Specifications – Banner SureCross DX81 User Manual

Page 2

Advertising
background image

1. Unplug the battery device from the SureCross device it powers.
2. Remove the four screws mounting the battery pack face plate to the body and remove

the face plate.

3. Remove the discharged battery and replace with a new battery. Only use a 3.6V lithium

battery from Xeno, model number XL-205F.

4. Verify the battery’s positive and negative terminals align to the positive and negative ter-

minals of the battery holder mounted within the case. Caution: There is a risk of explo-
sion if the battery is replaced incorrectly.

5. After replacing the battery, allow up to 60 seconds for the device to power up.

When removing the battery, press the battery towards the negative terminal to compress the
spring. Pry up on the battery’s positive end to remove from the battery holder. Properly dispose
of your used battery according to local regulations by taking it to a hazardous waste collection
site, an e-waste disposal center, or any other facility qualified to accept lithium batteries.
As with all batteries, these are a fire, explosion, and severe burn hazard. Do not burn or expose
them to high temperatures. Do not recharge, crush, disassemble, or expose the contents to
water.

Replacement battery model number: BWA-BATT-001. For pricing and availability, contact Banner Engineering.

Specifications

General

Environmental

Estimated Battery Life

19,000 mA·hours

Housing

Polycarbonate housing and rotary dial cover; polyester
labels; EDPM rubber cover gasket; nitrile rubber, non-
sulphur cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)

Wiring Access

One 1/2-inch NPT with 5-pin Euro-style 150mm pigtail
QD

Rating

Rating: IEC IP67; NEMA 6; (See UL section below for
any applicable UL specifications)

Operating Conditions

Operating Temperature: −40 to +85° C
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)

Shock and Vibration

IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz

Refer to the SureCross® DX80 Wireless I/O Network product manual, Banner p/n 132607, for installation and waterproofing instructions.
Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.

Certifications

DX8x...C (External Wiring Terminal Models)

CSA: Class I, Division 2, Groups A, B, C, D (Ex/A Ex nA II T4); Certificate: 1921239

LCIE/ATEX: Zone 2 (II 3G / Ex nA IIC); Certificate: LCIE 10 ATEX 1012 X

SureCross DX81 FlexPower Supply Module

2

www.bannerengineering.com - tel: 763-544-3164

P/N 131596 Rev. E

Advertising