BCS Oil-Fired User Manual

Page 8

Advertising
background image

Oil-Fired BCS

Page 9

MEASURING THE OUTCOMING WATER TEMPERATURE, CON’T

WARNING: Hydrogen gas can be produced in a hot water system served by

a heater that has not been used for a long period of time (generally two

weeks or more). Hydrogen gas is extremely flammable. To reduce the risk

of injury, open the hot water faucet at the highest location in the house for several

minutes before using any electrical appliance connected to the

hot water system. If hydrogen is present, there may be an unusual sound

similar to air escaping through the pipe as the water begins to flow. Do

not smoke or allow an open flame near the faucet at the time it is open.

MAINTENANCE

Annual service of the BCS is suggested and biannual service is recommended. For
burner maintenance, follow the manufacturer’s instructions supplied with the burner.

1. Install a new burner nozzle of the correct rate and angle.

2. Clean and adjust the electrodes and inspect for cracks in the porcelain. Check for corro-

sion on the buss bars and ignitor terminals.

3. Change the fuel oil filter and have the oil tank checked for sediment. Clean the tank, if

necessary.

4. The system should be checked with combustion instruments for safe and efficient

operation.

5. Keep the oil tank full to prevent water vapor from collecting (especially during the

summer).

6. Regularly check the Balanced Flue for obstructions such as hornets’ nests. The end caps

are removable for cleaning. Check the inlet and outlet tubes for any blockage and make
sure the joints are sealed.

7. EVERY SIX TO 12 MONTHS: Drain the heater tank and inspect for sediment or lime accu-

mulation. Flush if necessary. If lime has accumulated, remove with a commercial com-
pound. Check your water softening equipment if lime is found. DO NOT ATTEMPT TO
HEAT HARD WATER. (See maintenance label on heater.)

8. Change the magnesium anode rods every six to 12 months or when they are

reduced to

3

8

" diameter. (See maintenance label on heater.) It is recommended that

your installer use PermaBond LH-050. Teflon tape should not be used when installing
magnesium or aluminum anode rods.

9. Open the relief valve test lever to flush out. Make sure it reseats itself.

10. If the heater is shut off in cold weather, drain the tank to prevent freezing.

Date

Time

Person running test

Set temp °F

Outlet temp °F

Page 8

Oil-Fired BCS

PLACE WATER SYSTEM IN OPERATION

1. Fill the tank with water, opening a hot water faucet to allow trapped air to escape from the

heater. Open the cold water inlet valves. Shut off each faucet as it delivers water that is free
of air. Inspect for leaks. Never operate an empty or partially full heater.

2. Be sure the oil tank is filled with #1 or #2 heating oil. Loosen the ignitor hold down screw

and swing the ignitor back open on the hinge. Rotate the blower wheel a few times to
loosen the pump shaft. Swing the ignitor closed and fasten.

3. Bleed air from the oil line by opening the bleed valve on the fuel pump. Attach a small

plastic tube to the bleed valve fitting on the pump and run to a gallon container. Turn on
the electricity and set the thermostat so the burner motor runs. The heater will not ignite
when the bleed valve is open. Bleed the line until the oil is completely clear, not milky or
opaque. The oil must be transparent and free of air bubbles and froth. To keep the burner
control from locking out while bleeding the pump, attach a jumper between the flame
detector terminals after starting the burner. Remove the jumper when finished. Shut the
bleed valve and the burner will ignite. Remove the plastic tubing. Set the pump pressure to
100 PSI.

4. Adjust the burner combustion air in accordance with the burner manufacturer’s instruc-

tions. Using combustion instruments, check the CO

2

and smoke. The CO

2

should be at least

10

1

2

% with 0-to-trace smoke on the Bacharach scale (see burner installation manual.) No

draft adjustment is required. Your Bock BCS water heater will operate under draft or low
positive pressure depending on installation.

5. While the burner is operating, disconnect one of the yellow cad cell wires. Check to see

that the burner control locks out in the time specified on the control. Reattach the wire
and reset the control. The burner should restart. Note: You may have to wait a minute
before resetting the control.

INSPECT THE INSTALLATION AND ADJUST THE CONTROLS

The thermostat has been adjusted to 120°F at the factory. Wait until thermostat has shut off
fuel to the burner. Wait 30 seconds following shut-off of fuel, then set thermostat to the high-
est temperature. The burner should relight. Set thermostat to the lowest temperature; the
burner should go out. The thermostat should be adjusted to the minimum setting that will
meet the hot water needs of the homeowner or commercial application.

CAUTION: There is a scald potential if the thermostat is set too high. The recommended

temperature setting for normal residential use is 120°F. If higher temperature settings

are needed for combined appliance applications or commercial use, an automatic

tempering valve must be installed on all domestic hot water lines. Should overheating

occur, or the fuel supply fail to shut off, turn off the electricity to the water heater.

MEASURING THE OUTCOMING WATER TEMPERATURE

The thermostat is factory set at 120°F for residential use. (See the caution above regarding tem-
perature variations.) It is the responsibility of the homeowner and installer to verify that the
installer follows the recommended quantitative testing for measuring the out-coming water
temperature. To make sure that the system works properly after installation and in the future,
it is recommended that the heater’s performance be measured and monitored. Run water out
of the tap nearest the heater until it comes out warm. Using a calibrated thermometer, take a
measurement. If the water is not at a suitable temperature for the installation, have a qualified
service person adjust the aquastat. Contact Bock for further information if needed.

This log (or a similar one) should be filled out as follows:

Advertising