Danger, Warning – Burnham MEGASTEAM MST288 User Manual

Page 33

Advertising
background image

33

A. GENERAL

1. Install wiring and electrically ground boiler in

accordance with requirements of the authority

having jurisdiction, or in absence of such

requirements the National Electrical Code, ANSI/

NFPA 70.

2. Refer to National Electric Code or Local Electric

Codes for proper size and type of wire required.

Follow Code.

3. A separate electrical circuit must be run from

the main electrical service with an over-current

device/disconnect in the circuit. A service switch is

recommended and may be required by some local

jurisdictions.

4. Use anti-short bushings on all wiring passing

through boiler jacket, junction boxes and/or control

boxes.

5. Use armored cable (BX) over all exposed line

voltage wiring.

SECTION VI: ELECTRICAL

6. If an Alliance™ SL indirect water heater is used,

use priority zoning. Do not use priority zoning for

Hydro-Air Systems.

7. Wiring should conform to Figure 18.

B. INSTALL A ROOM THERMOSTAT on an

inside wall about four feet above floor. Never install

thermostat on an outside wall or where it will be

influenced by drafts, hot or cold water pipes, lighting

fixtures, television, rays of the sun or near a fireplace.

Keep large furniture away from thermostat so there will

be free movement of room air around this control.

Heat Anticipator in Thermostat should be set to match

the requirements of the control to which it is connected.

See Figures 18 thru 20A for desired system and heat

anticipator setting. If system tends to overheat above

the thermostat's temperature setting, reduce heat

anticipator setting by .1 or .2 amps. If system tends to

short cycle without reaching desired room temperature,

increase heat anticipator setting by .1 or .2 amps.

DANGER

Positively assure all electrical connections are unpowered before attempting installation or service of

electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock

once power is turned off.

WARNING

Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be from more than one source. Make sure all power is off before attempting any

electrical work.
Each boiler must be protected with a properly sized fused disconnect.
Never jump out or make inoperative any safety or operating controls.

WARNING

The interrupted hot (red) wire must be connected to the L terminal, the neutral (white) wire must be connected

to the N terminal and the constant hot (black) wire must be connected to the auxiliary terminal or the primary

safety control will be damaged.

Advertising
This manual is related to the following products: