6.

Enter the desired WATER FLOW
calibration factor by pressing the
INCREASE or DECREASE buttons
( or ) to change the value of the
flashing digit. (See Figure 4.)

Press the red ON/OFF button ( ) to
select the next digit – it begins flashing.
(See Figure 4a.)

7.

Press and hold the DISPLAY button
(

i

) until PASS is shown. (See Figure 1

on preceding page.)

8.

With the DISPLAY button (

i

) pressed,

press the DECREASE and INCREASE
buttons in this order: DECREASE,
INCREASE, DECREASE, INCREASE
( ). (See Figure 5 in the next
column.)

The right-most decimal flashes with
each INCREASE and DECREASE
button press.

9.

Release the DISPLAY button (

i

).

The display shows ScAL and resumes
normal operation. (See Figure 6.)

10.

Direct water and foam calibration is
now complete.

DDDDD

DDDDD

DDDDD

DDDDD

Manual p/n: 113965 Rev -, 04/11/2006

Figure

5

DDDDD

DDDDD

Figure

6

Figure

4

Figure

4a