Using the INCREASE and DE-
CREASE buttons ( or ), set the flow
rate to the actual known flow rate.

6.

Press the DISPLAY (

i

) button to view

the water flow calibration factor. (See
Figure 5.) Write this number down for
future reference.

7.

Press and hold the DISPLAY (

i

)

button until PASS is shown. (See
Figure 1 on the preceding page.)

8.

With the DISPLAY button (

i

) pressed,

press the INCREASE ( ) button 4
times.

A u is shown with each INCREASE
button press. (See Figure 6 in the
next column.)

DDDDD

DDDDD

9.

Release the DISPLAY (

i

) button. The

display shows ScAL for approximately
5 seconds. The unit is reinitialized
and the calibration factor is saved.
(See Figure 7.)

10.

Water flow calibration is complete.

Manual p/n: 113968 Rev -, 04/11/2006