Maintenance, Routine service, Battery maintenance – Snorkel TM12-sn1141-4999 User Manual

Page 6: Battery charging

Advertising
background image

6

Routine Service

Use the following table as a guide for routine
maintenance, refer to the Service Manual for
complete service instructions.

SERVICE OPERATION

INTERVAL

Monthly 6 Months 2 Years

Daily

or

or

or

50 Hrs. 250 Hrs. 1000 Hrs.

Clean entire work platform

X

Check battery fluid level

X

Charge batteries

X

Check tyres for damage

X

Check hydraulic fluid level

X

Check for peeling, faded or

X

missing labels & replace

Check deck and guardrail

X

fasteners for proper torque

Inspect elevating assembly

X

for dents or cracks

Check for & repair collision

X

damage

Check emergency lowering

X

valve operation

Check electric motor

X

brushes

Change hydraulic filter

X

Check all fasteners for

X

proper torque

Change hydraulic fluid

X

Maintenance

Never perform service on the work platform
while the platform is elevated.

Note: No normal (routine) maintenance on the
TM12 should require the platform to be raised.

Figure 6: Chassis Module, Right Side

Green LED

Indicator

Charger Plug

Cutout

Battery Maintenance

Hazard of explosive gas mixture. Keep
sparks, flame and smoking materials away
from batteries.
Always wear safety glasses when working
with batteries.
Battery fluid is highly corrosive. Rinse
away any spilled fluid thoroughly with clean
water.
Always replace batteries with UpRight
batteries or manufacturer approved replace-
ments weighing at least 28 kg (62 lbs.) each.

Check battery fluid level daily, especially if work
platform is being used in a warm, dry climate.

If electrolyte level is lower than 10 mm (

3

/

8

in.) above

plates add distilled water only. DO NOT use tap water
with high mineral content it will shorten battery life.

Keep terminals and tops of batteries clean.

Refer to the Service Manual to extend battery life
and for complete service instructions.

Battery Charging

Charge batteries at end of each work shift or
sooner if batteries have been discharged.

Charge batteries in a well ventilated area.

Do not charge batteries when the work
platform is in an area containing sparks or
flames.

Permanent damage to batteries will result if
batteries are not immediately recharged
after discharging.

Never leave charger operating unattended
for more than two days.

Never disconnect cables from batteries
when charger is operating.

Keep charger dry.

1. Check battery fluid level. If electrolyte level is

lower than 10 mm (

3

/

8

in.) above plates add

distilled water only.

2. Verify charger voltage switch is set to the

correct voltage.

3. Connect extension cord (1.5 mm² (12 guage)

conductor minimum and 15 m (50 ft.) in length
maximum) to charger plug located through
cutout at the left side of the chassis (Figure 6).
Connect extension cord to properly grounded
outlet of proper voltage and frequency.

4. Charger turns on automatically after a short

delay, the LED charge indicator will illuminate.

5. Charger turns off automatically when batteries

are fully charged, the LED charge indicator will
blink.

Advertising