Shutter motor, End switch for motor operated shutter – Aerovent IM-105 User Manual

Page 2

Advertising
background image

Shutter Motor

Damper

Motor

115V

115V

Supply

Fan

Motor

Fan Switch

Secondary

Low Volt Terminal

Transformer

Primary

Fan

Motor

Fan Switch

Damper

Motor

115V

230V or 460V

Supply

End Switch For Motor Operated Shutter

END SWITCH

MOTOR

Allen-Bradley 802TAW1

(Not Furnished)

Multi-Products 2027

Built In

Honeywell M4182 (Single Shaft)

Honeywell M4185 (Dual Shaft)

Built In

Barber-Colman MA418-500

Fan

Motor

C

E

To Be Grounded

By User If

Conditions Permit

3A

3A

Off

On

B

D

480V

240V

A

Disconnect

Switch

115V

F-Typ.

115 Volt Control Circuit

Airflow

Airflow

MOTOR-OPERATED, END-PIVOT:

For vertical or horizontal airflow. Exhaust only.

Motor operated shutters used in air-handling systems should

be wired to allow the shutter to open before the fan is started.

A shutter end switch should be mounted in the fan starter

circuit. The shutter end switch may be one of two types:

1.

LEVER OR LINKAGE ACTUATED: Allen Bradley

802TAW1 or equal. Mount switch to be actuated by shutter

linkage or shutter leaf when shutter is approximately 80%

to 90% open.

2.

MOTOR MOUNTED AUXILIARY SWITCH: Switch

mounts on side of motor opposite shutter linkage and is

actuated by shaft. Set so cam actuates switch when shutter

is 80% to 90% open.

The following end switches can be used on various motors.

A. Control Transformer (115V Secondary)

B. On-Off Selector Switch

C. Shutter Motor (115V)

D. Shutter End Switch

E. Holding Coil — Fan Starter (115V)

F. Thermal Overload Contactors

All shutter motors operated on 115 volts.

MOTOR-OPERATED, CENTER-PIVOT:

Designed for supply and exhaust.

Aerovent | www.Aerovent.com

5959 trenton Lane n | minneapolis, mn 55442 | Phone: 763-551-7500 | Fax: 763-551-7501

®

Advertising