SECTION 6 - JLG CONTROL SYSTEM
6-108
– JLG Lift –
3121256
Figure 6-27. CANbus Connections - Sheet 3 of 4
Remove Ground Module J7 plug
and measure the A & B pin of the
T fitting. This should measure
approximately 60 Ohms for a
complete CANbus Circuit.
Ground Module J7
(Black) plug
Boom Length &
Angle Module
CANbus Link
Platform Module
J7 (Black) plug