5

400/450 Series Connector Strip Assembly Instructions

Electrical Connections

-From End Plates Each end plate has
(4) .125” diameter pilot holes. These pilot
holes act as centers for optimal positioning of
holes up to 2.5” in diameter for attaching wiring
strain relief devices into connector strips. Use
the pilot hole to drill the required size for a
Greenlee® or equivalent punch to obtain
proper hole size for your installation require-
ments. Use 1st hole from the top for data in-
put, and 3rd hole from the top for AC power
connection.

WARNING: This equipment MUST be grounded. Never defeat the ground conductor or
operate the equipment in the absence of a suitably installed ground conductor. Contact
the appropriate electrical inspection authority or an electrician if you are uncertain that
suitable grounding is available.

Trade

Size

Hole Diameter

Required

1/2

.875

3/4

1.125

1”

1.375

1-1/4”

1.750”

1-1/2”

2.000”

2”

2.500”

Attaching Wires to Spring Clamp Type Terminal Blocks. (15A-50A Circuits Only)
20 Amp circuits are gray in color with white marking labels that accept up to maximum
8 AWG wire.

Step 1. Insert 1/8” wide flat blade screwdriver (supplied) into the square slot and push

all the way down so that screwdriver bottoms out.

Step 2. Insert the stripped wire into the oblong shaped hole.
Step 3. Remove screw driver to release spring clamp.
Step 4. Repeat steps 1-3 for all remaining connections.

DIN Rail Terminal Block System
The connector strip uses a 35MM
DIN rail modular terminal block sys-
tem. Terminal blocks range from 15
amps to 115 amps depending on
product configuration when ordered.

30A Screw Terminal Blocks
(Orange, 2 shown)

50A
Spring Clamp Terminal
Blocks (Gray or Beige, 12

50A Screw Terminal Blocks
(Blue, 2 shown)

75A Screw Terminal Blocks
(Yellow, 2 shown)

115A Screw Terminal Blocks
(Black, 2 shown)

35MM DIN Rail

End Stop (2)

Strain Relief Sizes

WARNING: ALL ELECTRICAL WIRING AND CONNECTIONS MUST BE PERFORMED BY A
QUALIFIED ELECTRICIAN.

Contractor ground lug
4-14 AWG

*Note: 1st two terminal blocks
(beige or gray) are used to
power DMX/RDM Opto-Isolators
and Ethernet modules if so
equipped. This circuit requires a
constant, non dimmable source
of power.

*15A or 25A Spring Clamp
Terminal Blocks (Beige or Gray,
2 shown) For Data Power
Supply

Color

Amps

Wire

Size

Strip

Lengt

h

Beige*

15A

14 AWG

1/2”

Gray**

50A

8 AWG**

1/2”

Orange

35A

10 AWG

3/8”

Blue

50A

8 AWG

1/2”

Yellow

65A

6 AWG

1/2”

Black

115A

2 AWG

3/4”

Beige**

50A

8 AWG

1/2”

Terminal Block Sizes

Note: Not all terminal blocks listed in chart below
may be present in connector strip.

**Note: 50A spring clamp terminal blocks are used for 20A circuits.
The upsizing allows for contactors to use #10AWG or #8 AWG line
feed wire. All load side components are rated at 20A.

S

p

rin

g

C

la

m

p

S

c

re

w

T

e

rm

in

a

l

-From Top The top surface at each end of
the connector strip has .875” knockouts.
Note: Minimal top clearance with double
pipe type brackets.

Optional Extended Terminal Box
(400 Series 13 circuits or more.)
(450Series 25 circuits or more.)

End Plates

400/450* Series is UL
and cUL listed under
File E31501 for Stage
and Studio.