Installation instructions for AF-U-20 & AF-U-Q30 Series

RV-1435

Figure 1

READ ALL OF THESE INSTALLATION INSTRUCTIONS BEFORE INSTALLING THE FIXTURE. FAILURE TO FOLLOW
INSTALLATION INSTRUCTIONS AND ALL APPLICABLE ELECTRICAL CODES WILL VOID THE PRODUCT WARRANTY.

WARNING:

These products may represent a possible shock or fire hazard if improperly installed or attached in any

way. Products should be installed in accordance with these instructions, current electrical codes and/or

the current National Electric Code (NEC).
WARNING:

Disconnect supply power from the source prior to installation. This product must be installed by a person

familiar with the construction and operation of the product and the hazards involved, and in accordance

with current electrical codes and/or the current National Electric Code (NEC). Consult a local licensed

electrician if you are not sure about the installation. To reduce potential of electric shock, fixture must be

grounded. The electrical input of this product is 120-277V AC. The installer must determine whether

power supply in in the range of 120-277V AC at the luminaire before installation.
Do not mount or support these fixtures in a manner that can cut the outer jacket or damage the wire

insulations. Do not restrict fixture ventilation. Do not cover fixtures with insulation or any material that

will impede air flow around and heat dissipation of the fixtures.

APPLICATION / USE:

This product is suitable for use in wet locations and designed for surface mounting only. This fixture is

suitable for installation where ambient temperatures do not exceed 104˚F (40˚C) during anticipated

hours of fixture operation.

ADDITIONAL SAFETY MEASURES:
1. LEDs are not serviceable. Do not attempt to open the fixture or LED compartment.
2. LEDs are bright. Do not look directly into fixture.
3. Not intended for recess mounting in any type of installation.
4. Do not use with wall dimmers or in dimming circuits.
Note: These instructions do not cover all details or variations in equipment nor do they provide
for every possible situation during installation, operation or maintenance.

Side bolts

INSTALLATION:

Disconnect supply power from the source prior to installation.

Installation requires T15 Security Torx Bit (AF-U-20) or T30 Security Torx

Bit (AF-U-Q30)

1. Remove old fixture if applicable.

2. Attach fixture to desired bracketry, if applicable, via the holes in

the yoke using corrosion resistant 3/8” bolt, lock washer and

nut (not provided); or lag screw. See Figure 1.

Mark positions of mounting holes and drill with appropriately

sized bit. Attach bolts, then tighten nuts securely applying

proper torque. Yoke can be used with a variety of durable,

corrosion resistant bracketry that can support fixture’s weight.

3. Attach weatherproof compression fitting to weatherproof

junction box cover and route jacketed lead wire through fitting.

Use appropriate weatherproof junction box cover and

weatherproof fittings.

4. Connect fixture’s lead wires to AC supply wires using

appropriate UL Listed electrical connectors as follows:

Connect line voltage (hot) AC supply wire (Black) to the line voltage AC wire (Black); connect neutral

(common) AC supply wire (White) to the neutral AC wire (White); and connect the ground AC supply wire

(Green or bare wire) to the ground AC wire (Green wire).

5. To aim the light, loosen the side bolts connected to the yoke mounting bracket and adjust the the fixture

up or down. Re-tighten side bolts to secure the fixture in the desired position. See Figure 1.

WARNING: Driver is designed for 120-277 volts. This fixture is NOT suitable for 480V applications.