Wiring Diagram for Dual Level Empty/Fill

Outfl ow control (Select Sw: H. ON side)
(a) When the l

1

switch actuate as level falls, relay energize.

(b) When the l

1

switch de-actuate as level rises, relay energize.

(c) When the l

2

switch de-actuate as level rises, relay de-energize.

(d) When the l

2

switch actuate as level falls, relay de-energize.

Infl ow control (Select Sw: L. ON side)
(a) When the l

2

switch actuate as level falls, relay energize.

(b) When the l

2

switch de-actuate as level rises, relay energize.

(c) When the l

1

switch de-actuate as level rises, relay de-energize.

(d) When the l

1

switch actuate as level falls, relay de-energize.