APG RCU-7000 user manual User Manual
Page 12
RCU-7000 Series
Rev. A1, 4/07
12
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Wiring Diagram for Dual Level Empty/Fill
Outfl ow control (Select Sw: H. ON side)
(a) When the l
1
switch actuate as level falls, relay energize.
(b) When the l
1
switch de-actuate as level rises, relay energize.
(c) When the l
2
switch de-actuate as level rises, relay de-energize.
(d) When the l
2
switch actuate as level falls, relay de-energize.
Infl ow control (Select Sw: L. ON side)
(a) When the l
2
switch actuate as level falls, relay energize.
(b) When the l
2
switch de-actuate as level rises, relay energize.
(c) When the l
1
switch de-actuate as level rises, relay de-energize.
(d) When the l
1
switch actuate as level falls, relay de-energize.