Led wts button, Figure 4 - wts internal view – Beckett AQUASMART 7600WTM User Manual

Page 6

Advertising
background image

6

Navigate to screen 2. The signal strength
screen indicates the strength of the
connection between the AWM and WTS.
At least 3 darkened bars are
recommended for operation, with 6 or
more indicating a good connection.
Moving the WTS closer to the AWM or
away from large metal object can improve
the connection.

On older AquaSmart controls, the OTR
may be off by default. Refer to the OTR
ON/OFF section of the Programming
Basic Functions Section

to make sure it

is turned on.

If modifying the default settings is desired,
refer to

the

Programming Basic

Functions

Section.

c.

6.

7.

The screen should display the current
outdoor temperature and show that the
last transmission was received within the
last few minutes. If “NOT INSTALD”
appears, the AWM and AquaSmart are
not communicating. Wait 30 seconds. If
the error persists, power down the
AquaSmart control, ensure the AWM is
properly connected, and restore power to
the control. If the OAT screen says “0F
AS OF 18:12 AGO”, press the WTS
button once. If the value does not
update, there is a problem with the
connectivity of the WTS. Move the WTS
to a location closer to the AWM or with
less interference.

Figure 4 - WTS Internal View

LED

WTS Button

WARNING! Mount with battery at bottom position only.

Failure to do so could expose the battery to water.

Advertising
This manual is related to the following products: