Blue Sea Systems PB-Series GFCI Breaker User Manual

Pb-series gfci breaker instruction bulletin

Advertising
background image

IST-0004

Rev. C

DANGER! Hazardous voltage. Can cause death or
serious injury. Turn off and lock out power supply
before installing PB-Series GFCI Breaker.

SAFETY INSTRUCTIONS:
• The GFCI will not protect a person against a line to

line shock hazard.

• To minimize false tripping: Do not connect to

swimming pool equipment installed prior to adoption
of the 1965 National Electrical code.

• Do not ground neutral on the Load Side of the GFCI.
• Test GFCI once a month. See test instructions

below.

• Not for use in portable or cord-connected

applications. Use only in permanently installed
enclosures.

• Do not subject to megger, high voltage or hi-pot test.

Remove ground fault circuit breaker before hi-potting
occurs on the circuit or system. (Ref. Sect. 550-12,
NEC).

• Do not reverse Line and Load connections.

INSTALLATION PROCEDURE:
1. The GFCI Breaker should be installed by a qualified

electrician.

2. Turn “OFF” and lock out the power to enclosure in

which GFCI is to be installed.

3. Turn “OFF” the GFCI Breaker handle.
4. Feed wires connected to the Load(s) through the

“Donut” and connect to Load Terminal(s) of the
Breaker and the Load Neutral to the Panel neutral
Bar (See Fig. A for wiring schemes).

5. Connect corresponding Hot wires directly to the

Breaker Line Terminals.

6. Connect the white “pigtail” neutral wire of GFCI

module to the panel Neutral Bar (see Fig. A).

7.

Mount GFCI Breaker to front panel and mount front
panel to enclosure.

FIG. A

8.

Turn “ON” power and turn “ON” breaker handle.
Test the GFCI as per test instructions below.

9. Place Monthly Test Reminder label in a convenient

place near the or on the panel and instruct
equipment users on test procedures and the
importance of performing and recording monthly
tests.

TEST INSTRUCTIONS:
1. Turn on the power to the panel.
2. Turn “ON” the GFCI breaker handle.
3. Depress the “TEST MONTHLY” button. This will

cause the handle to move to the “OFF” position
indicating that the GFCI is functioning properly. If the
handle fails to move to the “OFF” position the unit
MUST be replaced.

4. Restore power by moving the Breaker handle to the

“ON” position.

5. This test is to be performed on a monthly basis and

recorded on the “Monthly Test Reminder” label.

WHEN GFCI TRIPS:
The PB-Series GFCI breaker opens the circuit when
there is an overload or ground fault condition. When
tripping occurs perform the following steps:
1. Some faults are self-clearing. Try resetting the

breaker once.

2. If breaker continues to trip, the device is performing

its intended protection function, which means that a
hazardous condition could exist. A qualified
electrician should be called to evaluate the circuit.

PB-Series GFCI Breaker Instruction Bulletin

AC S OURCE

LOAD

HOT

(2)

LOAD

HOT

(1)

SYSTEMNEUTRAL

120 V AC LOAD

SYSTEMNEUTRAL

LINE /

SOURCE (2)

120 V AC LOAD

LINE /SOURCE (1)

120 VAC LOAD

SYSTEM NEUTRAL

120 VAC LOAD

LINE/SYSTEM
NEUTRAL

GFCI

MODULE

PIGTAIL

SYSTEMNEUTRAL

AC S OURCE

LOAD

HOT

LOAD
NEUTRAL

LINE/SOURCE

(HOT)

120 VAC LOAD

AC SOURCE

120/240 VAC WITH SWITCHED NEUTRAL

LINE/

SOURCE (2)

LINE/

SYSTEM
NEUTRAL

LOAD

NEUTRAL

120 VAC WITH SWITCHED NEUTRAL

ALTERNATIVE PIGTAIL

CONNECTION

AC SOURCE

LINE/SOURCE

(HOT)

120 VAC WITHOUT SWITCHED NEUTRAL

120/240 VAC WITHOUT SWITCHED NEUTRAL

LOAD

HOT

(1)

LOAD

HOT

(2)

LOAD

HOT

240 VAC LOAD

GFCI

MODULE

PIGTAIL

GFCI

MODULE

PIGTAIL

120 V AC LOAD

240 V AC LOAD

LINE/SOURCE (1)

GFCI

MODULE

PIGTAIL

Advertising