Maintenance and service procedures – Carlin 201GAS User Manual

Page 15

Advertising
background image

Model 201GAS burner — Instruction manual

Carlin part number MN201GAS Rev. 03/14/11

– 15 –

Where appliance instructions differ from this manual, follow the appliance instructions.

6. Maintenance and service procedures

Annual start-up & service

This burner should be started and serviced at least annually

by a qualified service technician. Failure to properly maintain
and service the burner could result in severe personal injury,
death or substantial property damage.

Turn off power to appliance and close main manual gas

valve when servicing burner. See WARNINGS on page 2
and elsewhere in this manual regarding correct procedures.
Failure to comply could result in severe personal injury, death
or substantial property damage.

Annual start-up and service procedures

Discuss burner/appliance operation with user to determine any prob-

lems that may have occurred during the previous season and to verify

user is aware of proper operation and care of the burner/appliance.

Turn off power to appliance and close main manual gas valve.

Remove burner from appliance and inspect diffuser plate, ignitor

electrode and flame rod (see Figures 5 and 6, page 8).

Remove ignitor electrode/flame rod assembly to clean and adjust if

necessary.

To remove assembly:

1. Remove the connector wires from the flame rod and ignitor electrode.
2. Remove the bolt securing the yoke to the housing.
3. Pull the electrode/flame rod assembly straight back and out.
4. Clean the assembly if necessary. Replace any part that is damaged.
5. Check the dimensions of the assembly against those shown in Figure 6,

page 8. Adjust if necessary.

6. Replace the electrode/flame rod assembly in the air tube.
7. Tighten the retaining bolt to secure the yoke in place.

If the inside surface of the air tube and/or diffuser plate needs

to be cleaned, clean with a vacuum cleaner with brush at-
tachment while the electrode/flame rod assembly is out of
the burner.

Verify that hinged cover gasket is closed and screw is tight.

Close the housing cover plate and secure in place.

Check the burner flange gasket. It must be in good condition. Replace

gasket on burner flange and mount burner in appliance, securing to

mounting studs.

Perform the complete checkout procedures of pages 11 through 15,

including system inspection and checks.

Advertising