2remote control setup (continued), F1 3 setup sequence, 3 company contact – BEA IS40 User Manual

Page 2

Advertising
background image

Page 2 of 2

75.5376.01 EN 20080505 (75.5375)

2

Remote Control Setup (Continued)

FUNCTION

AFFECTS

INFRARED OR

MICROWAVE

REMOTE

CONTROL

BUTTON

FUNCTION DESCRIPTION

SENSITIVITY

MICROWAVE

0-9: (7-Default)

DETECTION MODE

MICROWAVE

1: Bidirectional (Towards or Away from Sensor)
2: Unidirectional Approach (Towards Sensor)
3: Unidirectional Depart (Away from Sensor)

REJECTION MODE

MICROWAVE

1: Detection of all Kind of Targets in Motion

2: Detection of all Kind of Targets in Motion + Interference Immunity
3: Low ‘Pedestrian/Parallel traffi c’ Rejection + Interference Immunity
4: Medium ‘Pedestrian/Parallel traffi c’ Rejection + Interference Immunity
5: High ‘Pedestrian/Parallel traffi c’ Rejection + Interference Immunity

ACTIVATION
RELAY
HOLD TIME

INFRARED

MICROWAVE

0: 0.5 second
1: 1.0 second
2: 2.0 seconds
3: 3.0 seconds

4: 4.0 seconds
5: 5.0 seconds
6: 6.0 seconds

7: 7.0 seconds
8: 8.0 seconds
9: 9.0 seconds

RELAY
CONFIGURATION

INFRARED

MICROWAVE

OUTPUT
CONFIGURATION

INFRARED

MICROWAVE

PRESENCE RELAY

IS40

IS40P

0 - 4: ALL MODES

Activates when object is in
presence zone.

Activates when object
is in presence zone.

ACTIVATION RELAY

IS40

IS40P

0: STANDARD MODE

Activates when motion detected.

Activates when object
is in presence zone.

1: PULSE ON ENTRY

Activates if object motion is
detected and then object enters
presence zone.

Activates when object
enters presence zone.

2: PULSE ON EXIT

Activates if object motion is
detected and then object exits
presence zone.

Activates when object
exits presence zone.

3: PULSE ON ENTRY
FIRST / LAST LINE
(See Example to the Left)

Activates if object motion is
detected and then object enters
presence zone (fi rst or last line).

Activates when object
enters presence zone
(fi rst or last line).

4: PULSE ON EXIT
FIRST / LAST LINE
(See Example to the Left)

Activates if object motion is
detected and then object exits
presence zone (fi rst or last line).

Activates when object
exits presence zone
(fi rst or last line).

SETUP

INFRARED

MICROWAVE

Initiate Setup, press

DEFAULT VALUES

INFRARED

MICROWAVE

Set Factory Defaults, press

F1

F1

3

Setup Sequence

1. Power on the sensor. Sensor automatically performs a Setup on power up and Setup is complete when Red/Green fl ashing stops.

2. If the Detection Zone (Background) permanently changes and a new Setup is required, perform a new Setup by pressing

. Red & Green LEDs will blink rapidly until setup is complete.

NOTE: Avoid movement in the IR zone during setup.

Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, please
call BEA, Inc. If you must wait for the following workday to call BEA., leave the door inoperable until satisfactory repairs
can be made. Never sacrifi ce the safe operation of the automatic door or gate for an incomplete solution. The following
numbers can be called 24 hours a day, 7 days a week. For more information, visit www.beasensors.com.

US and Canada:

Canada:

Northeast:

1-866-249-7937
1-866-836-1863
1-866-836-1863

Southeast:

Midwest:

West:

1-800-407-4545
1-888-308-8843
1-888-419-2564

Description

Active

Passive

Detection

COM

COM

No Detection

COM

COM

NO

NC

NO

NC

NO

NC

NO

NC

Activation

Relay

Presence

Relay

1

Active

Passive

2

Passive

Active

3

Passive

Passive

4

Active

Active

3 Company Contact

DOOR EXAMPLE

LAST LINE

FIRST LINE

6 3 0 3 6

3

6

9

12

15

18

Height = 16 ft.

S = 3

S = 9

S = 6

FT.

Sensitivity 9, 6, 3

9

0

0

0