Major Components

1. Submersible Turbine Effluent Pump - A submersible turbine

effluent pump is a multistage centrifugal design pump. Each stage

consists of an impeller and diffuser. Water pressure increases in

equal amounts as it passes from stage to stage. The more stages,

the higher the pressure the pump will develop.

To correctly select a pump for a specific application, the following

information must be known:

• The amount of discharge required in GPM or LPM

• The total dynamic head required in feet or meters

Use this information along with the performance data found on the

previous page to make your selection.

2. Controls - Submersible turbine effluent pumps require the use of

an above ground control panel or junction box with a pump control

switch for proper operation. Operation of these pumps without a

control panel or junction box with a pump control switch can result in

failure of the pump and void the warranty. At least three elevations

must be determined to control a pump within a given tank or basin:

pump on level, pump off level and high water alarm level.

3. Piping - The submersible turbine effluent pump can be installed with

schedule 40 PVC pipe. The pipe size should be 1¼” diameter for

the 11 GPM to 27 GPM pump series and 2” diameter for the 35-85

GPM pump series.

General piping from the pump to a splitter, distribution box, drain

field etc., should be the same diameter as stated above. For long

pipe runs consult friction loss tables for correct pipe sizing.

4. Check Valve - A check valve is required in all duplex systems. It is

also required when a large amount of effluent can backflush into the

system causing rapid cycling of the pump.

A 1/8” weep hole must be drilled in the side of the discharge

head when using a check valve (see drawing below for drill

location).

Electrical Data for Clarus Environmental Turbine Effluent Pumps

locked

fuse/Circuit

winding

Maximum

Rotor

kVA breaker Amps

Resistance

hP

Volts Phase hz S.f. Amps watts

Amps

Code Std.

Delay

line to line

1/2

115

1

60 1.6

12

970

64.4

R

30

15

1.0 - 1.3

1/2

230

1

60 1.6

6

970

32.2

R

15

8

4.2 - 5.2

3/4

230

1

60 1.5

8

1325

40.7

N

20

10

3.0 - 3.6

1

230

1

60 1.4

10.4

1600

48.7

N

25

11

2.2 - 2.7

1 1/2

230

1

60 1.3

13.1

2250

56.8

L

35

15

1.5 - 1.9

2

230

1

60 1.25 Y 13.2

2650

51.0

G

30

15

1.6 - 2.3 M

B 11.9

5.2 - 7.15 S

R 2.6

3

230

1

60 1.15 Y 14.0

3650

82.0

G

45

20

.9 - 1.5 M

B 14.5

3.0 - 4.9 S

R 4.5

35-85 GPM MODELS

11-27 GPM MODELS