Installation procedure, Load rating information – Condux Hooked Hanger Sheave User Manual

Page 2

Advertising
background image

1. Choose the correct size sheave depending upon the cable’s outer

diameter and the cable manufacturer’s recommended cable bending

radius. Refer to the Condux Cable Installation Equipment & Tools

Catalog for sheave dimensions.

2. Hang the

sheave in the manhole using a rope attached to the

sheave support arm. Position the sheave so that the cable

contacts the sheave in a horizontal line.

3. Attach a

load-rated chain between the sheave tie-down arm and

a

pulling-in iron. If no pulling-in irons are present or usable, use a

Condux Jamb Skid.

4. If the sheave is angled away from the duct, use a Condux

alignment arm to keep the cable from jumping off the sheave.

For installation or removal from existing cables, the sheave tie-down arm

can be split and swung out of the way. Simply remove a locking pin from

the side of the arm and swing the yoke out of the way. Only the supplied

locking pin or grade 8 bolt should be used to lock yoke to arm.

Installation Procedure

!WARNING: Read, understand, and save all

procedure and safety instructions before using any

Condux

®

Hooked Hanger Sheave. Failure to do so

could result in personal injury or property damage.

Save this user’s guide for future reference.
!ADVERTENCIA: Favor de leer y comprender todas

las instrucciones de operación y seguridad antes

de usar el Condux

®

Hooked Hanger Sheave.

Si Ud. no comprende las instrucciones favor de

consultarle a su jefe.

ADVERTENCIA

Instrucciones

de Operación

Figure 1.

Hanging Installation

!WARNING: Do not exceed the load capacities of the

Condux

Hooked Hanger Sheave, the tie-down chain,

or the pulling-in iron. Severe personal injury or

property damage could result.

!CAUTION: Follow all manhole standard operating

procedures, including work area protection and gas

detection. Wear personal protective equipment: hard

hat, safety glasses, safety shoes, and leather work

gloves.

!WARNING: Do not remain in the manhole when

pulling cable. The cable is under tension. Severe

personal injury or death could result.

F = 10,000 lb.

F = 14,000 lb.

F = 10,000 lb.

F = 20,000 lb.

Figure 3. Force Applications

Load Rating Information

All Condux Hooked Hanger Sheaves are load rated for 10,000 pounds

of line tension. If used to guide cable around a 90° arc, the hanger arms

could be subjected up to 14,000 lbs of force. If used to guide cable

around a 180° arc, the hanger arms could be subjected up to 20,000 lbs

of force. All tie-down accessories must be load rated to handle these

pulling forces.

Figure 2.

Jamb Skid Installation

Sheave Support Arm

Alignment

Arm

Sheave

Sheave

Tie-down

Arm

Load-rated

Chain

Pulling-in Iron

Cable