Controller Sensors 851 Series User Manual

Model, Transducer installation

Advertising
background image

MODEL

851

TRANSDUCER

INSTALLATION

The Model 851 Pressure Transducer is a

compact instrument for measuring and

controlling the many different media that are

compatible with our sensing element. Each unit

is capable of measuring 4 full scale pressure

ranges and 3 or 4 split ranges. Each unit also

contains 3 output selections: 1-5 VDC, 1-10

VDC, and 4-20mA. Please see the spec sheet

for further information. All adjustments are

made outside the case and there are no jumpers

to lose!

I

NSTALLATION

1. Location- The model 851 pressure

transducer should be placed in as clean, dry and

vibration free a location as possible.
2. Pressure Connections- The 851 pressure

transducer uses 2 barbed fittings for use with

1/8” ID vinyl or rubber tubing. Attach tubing

from positive pressure or higher pressure

source to port marked

High (P1) and lower or

negative pressure to opposite port

(P2).

Arrange tubing to minimize stress on the

connections. If possible, mount with ports

facing down to aid in moisture drainage.
3. Mounting- Attach the Model 851

Transducer to the mounting surface using two

fasteners inserted through the two mounting

holes located on either the side mounting

flanges, or the holes at the top of the case.

Do

not overtighten.

(When selecting between ranges you may

need to adjust the zero using the offset pot

located next to the range selector switch.)

E

LECTRICAL

C

ONNECTIONS

All electrical connections to the 851 series

transducer are made to the pluggable screw

terminal block. The block is coded as follows.

1) +IN = Supply Positive, 2) COM = Supply

Negative, 3) +OUT = Signal Out.
An external power supply delivering 18 - 24

VDC/24 VAC with min. 10 mA is required to

drive the unit (30mA is required for a 4-20mA

output).

CAUTION:

Do not exceed specified

supply voltage.

Do not apply voltage to

“+OUT” terminal as permanent damage

will occur.

3

W

IRE

C

ONNECTION

• + Power Supply

• - Power Supply

Signal IN


CONTROLLER

+IN

COM

+OUT

3

WIRE TO

2

WIRE CONNECTION

+IN

COM

+OUT

• + Power Supply
• - Power Supply

• - Ctrl Negative
• Ctrl Ground

CONTROLLER

4 to 20 mA Output

O

FFSET

The 851 series transducer is factory zeroed. If it

should need adjustment upon arrival the offset

pot is located next to the range selector switch

on the side of the unit. With the transducer

installed and no pressure applied place a meter

in series with the supply negative (Ground), and

the signal out. Turn offset adjusting pot to

desired reading.

S

WITCH

S

ETTINGS

Ranges are set using the rotary switch on the

side of the device. Choose the setting number

that matches the desired range shown on the

label. (Note: the offset may need to be

readjusted.) Output types are selected using the

slide switch next to the terminal block.

C

USTOMER

S

ERVICE

If any problems are encountered during

installation please call the number below for

assistance.