The Model 560 Pressure Transducer is

available in both Differential and Gauge

configuration, in ranges from 0-2 to 0-500

PSI. This Transducer features a NEMA 4

enclosure and series 300 stainless steel

wetted parts making it compatible with

most wet and dry media. Pressures are

converted to three standard outputs, 0-5

VDC, 0-10 VDC and 4-20 mA with an

accuracy of +/- 0.5% F.S.O..

I

NSTALLATION

1. Location- the model 560 Pressure

Transducer should be placed in as dry and

vibration free a location as possible. If

possible, mount with connectors facing

down to aid in moisture drainage.

2. Pressure Connections- the 560 Series

Transducer uses 2 (Differential) or 1

(Gauge) 1/8” NPT female fittings. Always

use a wrench to hold the transducer

fittings while tightening the mating

connection.

3. Mounting- Attach the Model 560

Transducer using 4, 1/8” fasteners. The

mounting holes are located on the Four

Corners of the box, below the top cover.

E

LECTRICAL

C

ONNECTIONS

All electrical connections to the 560 series

Transducer are made to the internal four

wire terminal strip. An external power

supply delivering 24 VAC/24 VDC, with

a minimum of 35 mA is required to drive

the unit.

The four wire terminal strip supplied with

the 560 series Transducer is labeled as

follows, +IN (Supply Positive), -IN

(Supply Negative), OUT (Signal Out),

GND (Common to Supply Negative).

CAUTION:

Do not exceed specified

supply voltage.

Do not apply voltage

to

OUT terminal, as permanent

damage will occur.

3

W

IRE

C

ONNECTION

• + Power Supply

• - Power Supply

Signal IN


CONTROLLER

IN +

IN -

OUT

GND

3

WIRE TO

2

WIRE CONNECTION

IN +

IN -

OUT

GND

• + Power Supply
• - Power Supply

• Signal
• Ctrl Ground

CONTROLLER

4 to 20 mA Output

C

ONVERTING

4-20

M

A

TO

1-5VDC

560 Series Pressure Transducers with a 4-

20mA output can be easily adapted to

receivers requiring 1-5 VDC input. Insert

a 250 ohm resistor between the + and -

controller input terminals. This will safely

convert the 4 to 20 mA signal to the

desired voltage.

O

FFSET AND

S

PAN

Two adjustments are offered with the 560

series pressure transducer, offset and span.

After initial installation, the offset and

span can be adjusted by removing the top

cover and adjusting the labeled pots

located on the edge of the PCB. With the

transducer installed and no pressure

applied, place a meter between the supply

negative and the output terminal to set the

zero. Apply full-scale pressure and adjust

the span to the required voltage or current

reading. Repeat process until desired

reading is attained.

C

USTOMER

S

ERVICE

If any problems are encountered during

installation please call the number below

for assistance

Call 1-800-735-8998