Chromalox Instruments and Controls

A-51643 Rev. 6 10/06/03

20

5 Function Set Details

This section details the Modbus functions supported in the Protocol

TM

Plus controller.

5.1 Function Set Overview

Table 8 Protocol

TM

Plus Function and Exception Code Set

Function Code

Function Name

01

Read Outputs

02

Read Input Discretes

03

Read Holding Register (Read Multiple Registers)

04

Read Input Registers

06

Write Single Register

08

Diagnostics

16

Write Multiple Registers

17

Report Slave ID

Table 9 Protocol

TM

Plus Diagnostic (Function Code 08) Sub-function Set

Sub-function Code

Sub-function Name

Comments

00

Return Query Data

Loop Back

01

Restart Communications Options

Reset the slave. Cancels Listen Only

Mode.

02

Return Diagnostic Register

Contents of slave‘s 16-bit diagnostic

register.

04

Force Listen Only Mode

Reset by Restart Communications

Option

10

Clear Counters and Diagnostic Register

Also cleared at power up. Clears only

the counters

12

Return Bus Communication Error Count

Slave CRC errors only.

13

Return Bus Exception Error Count

Slave Exception Response count.

14

Return Slave Message Count

Number of messages addressed to the

slave and successfully processed.

Includes broadcast messages.