Det-Tronics X7050 xWatch Industrial Video Surveillance Camera User Manual

Page 9

Advertising
background image

3.1

95-8600

7

AIMIng ThE CAMErA
In installations where the Model X7050 Camera is used

for monitoring the same hazardous area as a single

detector, the recommended procedure for ensuring

that the camera is correctly aligned with the detector’s

cone of vision is to use a Cone of Vision Tester (Laser

Aimer) available from Detector Electronics Corporation

(Det-Tronics

®

).

1. Using the COV tester, locate the center of the

detector’s field of view. (Refer to the instruction

manual provided with the COV tester for complete

information regarding its use.)

2. Place the COV tester on the camera. Loosen the

mounting bracket, then adjust the center of the

camera’s field of view to match the center of the

detector’s field of view.

The COV tester can also be used to locate the outside

edge of the field of view.

LEVELIng ThE CAMErA
If the image on the monitor does not appear to be level,

this can be corrected by rotating the camera module

within the xWatch Camera.

1. Remove the housing cover from the xWatch Camera.

See Figure 5.

2. Loosen the setscrew on the side of the camera

module. See Figure 7.

3. Align the two notches on the face of the module so

that they are level with the horizon or until the image

on the monitor looks level.

4. When proper orientation has been achieved,

carefully tighten the setscrew. Do not overtighten.

LOOSEN SETSCREW
USING 5/64 INCH ALLEN WRENCH

TURN RING TO ALIGN THE TWO NOTCHES
LEVEL WITH HORIZON OR UNTIL IMAGE IS LEVEL

A2369

Figure 7—xWatch camera module