Calibration – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual

Page 40

Advertising
background image

H-3

95-8656

4.2

cAlibrAtion

To initiate calibration of the PIRECL from the UD10-DCU

Display:

1. Using the magnet to activate the switches on the

UD10-DCU display, navigate to the “Calibration”

menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Device Cal

Cal Gas Conc
Cal Gas Type
Calibration
Cal Date

Calibration

Execute
Abort

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10-DCU will display “Waiting for Zero” on

the main display screen, with a solid red LED on the

PIRECL housing illuminated.

4. The UD10-DCU will then display “Waiting for Gas”

on the screen, while the LED on the PIRECL is

flashing red.

5. Apply calibration gas to the PIRECL

6. The UD10-DCU will display “Waiting for Span” on

the screen, while a red flashing LED on the PIRECL

housing is illuminated.

7. When the UD10-DCU displays “Remove Cal Gas”

on the screen and the LED on the PIRECL housing

is off, remove the calibration gas.

8. After successful calibration, the UD10-DCU

automatically returns to the normal display with the

green LED illuminated on the PIRECL housing.

To initiate calibration from the PIRECL while monitoring

calibration using the UD10-DCU display:

1. Using the magnet, activate the magnetic calibration

switch on the PIRECL detector. See Figure below.

The LED turns from green to red.

2. The UD10-DCU will display “Waiting for Zero” on

the main display screen, with a solid red LED on the

PIRECL housing illuminated.

3. The UD10-DCU will then display “Waiting for Gas”

on the screen, while the LED on the PIRECL is

flashing red.

4. Apply calibration gas to the PIRECL detector.

5. The UD10-DCU will display “Waiting for Span” on

the screen, while a red flashing LED on the PIRECL

housing is illuminated.

6. When the UD10-DCU displays “Remove Cal Gas”

on the screen and the LED on the PIRECL housing

is off, remove the calibration gas.

7. After successful calibration, the UD10-DCU

automatically returns to the normal mode with the

green LED illuminated on the PIRECL

CALIBRATION MAGNET

CALIBRATION NOZZLE

MULTICOLOR LED

HART COMMUNICATION PORT

(COVER INSTALLED)

PLACE CALIBRATION MAGNET
HERE TO ACTIVATE INTERNAL
REED SWITCH

B2435

Model PIRECL Gas Detector