APPENDIX B

CSA APPROVAL

Refer to drawing 006880-001 (Figure B1) for applicable area classification and installation details.

COMBUSTIBLE

Transmitters

: U9500A1001, U9500A1004, with Junction Box P/N 006264-XXX.

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per CSA C22.2 #30,

and Ex d IIC T4 per CSA E60079-0, -1.

• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per CSA C22.2 #213.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.

Hydrocarbon Gas Transmitters

: U9500H6002 or U9500H6004, with Junction Box P/N 006264-XXX.

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per CSA C22.2 #30,

and Ex d IIC T4 per CSA E60079-0, -1.

• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per CSA C22.2 #213.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.

Sensor Termination Box

: Model STB Series, used with Electrochemical units above.

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)

Hazardous (Classified) Locations per CSA C22.2 #213.

• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per CSA C22.2 #94.

Combustible Gas Sensors

: Model CGS:

• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per CSA C22.2 #30.

Hydrocarbon Sensors

:

Model PIR9400:
• Explosion-proof for Class I, Division 1, Groups B, C and D (T5) Hazardous (Classified) Locations
• Class I, Division 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations, Tamb = –40°C to +75°C, conduit

seal not required.

Model PIRECL:
• Explosion-proof for Class I, Division 1, Groups B, C and D (T4) Ta = 75°C with intrinsically safe output for HART

Communications in accordance with control drawing 007283-001, conduit seal not required.

• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4) Ta = 75°C Hazardous (Classified) Locations.

Stand-alone 4-20 mA CSA Approved Gas Sensor/Transmitter:
• See specific detector rating.