Metering air valve troubleshooting – Bradley MF2922 User Manual

Page 13

Advertising
background image

Parts and Service Guide

Terreon

®

Multi-Fount Washfountains

Bradley Corporation 215-1447 Rev. F; EN 07-005A

13

1/30/2008

Metering Air Valve Troubleshooting

Problem: Valve will not shut off.

Cause: Timing mechanism is clogged.

Solution: Clean and inspect timing mechanism:

1. If compressed air is available, blow water and debris from timer cover of timing mechanism.

2. Turn adjusting screw out all the way. Clean and inspect screw and valve body.

3. Turn adjusting screw in to desired cycle time.

Problem: Valve will not turn on.

Cause: Water is not being supplied to unit.

Solution: Open all stops on mixing valve.

Cause: Water pressure is over 80 PSI.

Solution: Install a pressure reducing valve.

Cause: Failed diaphragm/magnet assembly.

Solution: Unscrew the valve clamp nut on valve. Remove valve cover. Gently press the the
diaphragm. The valve should activate. If not, replace the diaphragm/magnet assembly.

Problem: Timing can not be adjusted for more than 5 seconds.

Cause: There is an air leak

Solution: Check the valve assembly:

1. Check all tubing and fittings for proper assembly.

2. Tighten cap and nut on 1/8" tubing.

Problem: Pushbutton does not work properly.

Cause: Air volume may not be sufficient to operate valve.

Solution: Check for leaks and lubricate U-cup:

1. Check all fittings for air leaks.

2. Disassemble pushbutton and lubricate U-cup seal (see pushbutton assembly diagram on page 8).

Problem: Water is dripping from the streamformers.

Cause: Debris has accumulated on valve seat or orifices.

Solution: Clean and inspect valve seat.

1. Remove screws and disassemble metering valve.

2. Clean valve seat and inspect for deep gouges or scratches. Replace valve body if necessary.

3. Remove any debris clogging off-center hole in rubber diaphragm.

Advertising
This manual is related to the following products: