Operating, Tiller handle monitor 8500-02 and 8593-02, Maintenance & inspection – Elkhart Brass Vulcan 8593-xx User Manual

Page 7: Iller, Andle, Onitor, Heel, 8593-03/294-11rev.06, Ixed, 8500-03x

Advertising
background image

III. O

PERATING

1. Tiller Handle Monitor 8500-02 and 8593-02
Turn both left/right and up/down lock handles counterclockwise to
disengage lock. Move tiller handle to desired left/right and up/down
positions. Turn both lock handles clockwise to engage lock.
2. Dual Hand Wheel Monitor 8500-03 and 8593-03/294-11REV.06
The left/right and up/down hand wheels will rotate with the monitor. Turn
the up/down hand wheel clockwise to lower nozzle or counterclockwise to
raise nozzle. Turn the left/right hand wheel clockwise to move nozzle left
or counterclockwise to move nozzle right.
3. Dual Hand Wheel Fixed Base Monitor 8500-03X and 8593-
03X/294-11REV.06X
The left/right hand wheel remains fixed while the up/down hand wheel will
rotate with the monitor. Turn the up/down hand wheel clockwise to lower
nozzle or counterclockwise to raise nozzle. Turn the left/right hand wheel
clockwise to move nozzle left or counterclockwise to move nozzle right.

IV. M

AINTENANCE

& I

NSPECTION

The monitor should be inspected regularly. Careful inspection for damage to
the monitor or nozzle is especially important after use in emergency
operations.

Flow water to check nozzle pattern. If pattern is disrupted, remove nozzle and
check for debris lodged between the nozzle stem and body, or in the stream
shaper inlet.

During nozzle flow test, inspect monitor swivel joints for leaks.

Note: Although grease fittings are provided for the up-down and left-right
gear cases, routine greasing should not be necessary. If the monitor is
exposed to a high level of radiant heat for a prolonged period, it may be
possible for the factory grease to thin and run out of the gear cases. In such
an event, fresh grease should be applied.

Page 3

98428000 Rev. Rel

Advertising
This manual is related to the following products: