Troubleshooting Guide

This guide provides troubleshooting tips for the 7095 EXM CAN Stow Module. If the Stow Module still

does not work properly after checking the potential issues found in this guide, please contact Elkhart

Brass for further assistance.

CONFIGURATION ISSUES
The Stow Module only requires configuration if the monitor group number is NOT the same as that of

the Stow Module. Monitors and Stow Modules sold individually are configured to Group 1 by default,

and those should not need to be configured prior to installation. Those sold in packages or for multi-

monitor systems may have different group numbers. If you need to verify the Monitor Group number,

follow the steps under Operating Instructions step M. Write Diagnostic File* in an EXM monitor manual**.

If needed, the EXM CAN Stow Module’s group number can be changed, prior to installation, by following

the instructions below.

Ensure that proper Electrostatic Discharge (ESD)

precautions are taken and that the Stow Module is not

connected to a power supply.

Remove the cover of the Stow Module enclosure by

using a straight screwdriver to disengage the circuit

board header clips.

Find the Selection Switch “SW1” on the circuit board.

Using a straight screwdriver, carefully turn SW1 to the

desired Group Number minus one. (For example, if

you want to configure for a Group 3 Monitor, point the

SW1 arrow to 2). Standard setting is 0 for Group 1.

Carefully close the enclosure. Be sure the red seal is

not pinched or damaged when closing. Ensure both

clips click into place on either side of the enclosure.

The red seal should no longer be visible.

Install the Stow Module according to Installation

Instructions Step 1 – EXM CAN Stow Module in an EXM

monitor manual**.

*Operating Instruction step letter may not match ‘M’. In this case, refer to the section title “Write Diagnostic File” for instructions.

**EXM monitor manual refers to the Sidewinder EXM, Cobra EXM, Scorpion EXM, etc.