INSTRUCTIONS FOR ELKHART 8394N-03

DUAL HANDWHEEL MONITOR


INSTALLATION

Ensure that the alignment of the monitor base for the 8394N-03 is in the correct position for access to
the left/right hand wheel. Attach 4" 150 lb. class ANSI pattern companion flange to water supply pipe.
Elkhart Brass recommends using the 81317001 Companion Flange Kit. Attach monitor inlet flange to
companion flange on water supply pipe with eight (8) #316 stainless steel, 5/8-11 UNC grade 5 bolts,
2-1/2 inches long, with nuts. If a wafer type butterfly valve is installed between the monitor and the
companion flange, required bolt length will be 4-1/2 inches. Seal flange joint with gasket, or suitable
flange sealant. Most wafer type butterfly valves have seats that serve as flange gaskets, and
separate gaskets or sealant is not required. Apply Loctite® #242 to bolt threads, then thread on nuts,
and torque to 60-70 ft-lbs uniformly in increments of approximately 20ft-lbs.

Warning: When installing monitor on a raised face companion flange or butterfly valve, it is critical
that bolts be tightened uniformly to prevent cocking of the monitor relative to the flange or valve. If
the monitor becomes cocked, the monitor cast flange base will fracture and fail when the bolts on the
"high" side are tightened.

OPERATION

The left/right hand wheel remains fixed while the up/down hand wheel will rotate with the monitor.
Turn the up/down hand wheel clockwise to lower nozzle or counterclockwise to raise nozzle. Turn
the left/right hand wheel clockwise to move nozzle left or counterclockwise to move nozzle right. (See
drawing 98031050 for possible up/down and left/right travel stop positions.)

MAINTENANCE & INSPECTION

The monitor should be inspected regularly. Careful inspection for damage to the monitor or nozzle is
especially important after use in emergency operations.
Flow water to check nozzle pattern. If pattern is disrupted, remove nozzle and check for debris
lodged between the nozzle stem and body, or in the stream shaper inlet.
During nozzle flow test, inspect monitor swivel joints for leaks.

Note: Although grease fittings are provided for the up-down and left-right gear cases, routine
greasing should not be necessary. If the monitor is exposed to a high level of radiant heat for a
prolonged period, it may be possible for the factory grease to thin and run out of the gear cases. In
such an event, fresh grease should be applied.