Warning – Elkhart Brass SPIT-FIRE 08394053 Monitor User Manual

Page 5

Advertising
background image

5

OVERVIEW

Spit-Fire® Monitor Features:

Construction: All brass with vaned 4” waterway

Mounting Flange: 4” 150# flat-face ANSI flange raised face flange available as option

Discharge:

3½” NHT male outlet

Stream Shaper:

#284-B brass shaper included

Flow:

2000 GPM max flow @ 200 PSI max working pressure

Motors:

120 VAC NEMA 4 rated synchronous motors (non-arcing)

o

Constant torque and current output in start, running, and stall

o

UL Recognized for Class 1, Division 2 use

o

Will not cause damage or increase in current when motor is stalled

o

Instantaneous start, stop, and reverse

o

Residual (Power Off) torque is always present

o

Long life and exceptional reliability

o

120 VAC, 50/60 Hz., 1 Phase, 0.80 Amp current per motor

Junction Box: NEMA #4X (IP-66) water tight, corrosion resistant ATEX certified & UL listed

enclosure with terminals for hazardous locations. Stainless Steel motor

cable junction box with bracket to attach to monitor, flange base included.

Range of Motion: Monitor stops are factory set at 346° horizontal (+173° to -173° from front

center), and 135° vertical (+90° to -45°)

Rate of Horizontal Motion: 0.139 Sec/°

Manual Override: Hand wheels provided for vertical and horizontal movements. Hand wheel

will not rotate when monitor is operated electrically.

Meets NEC (NFPA 70) Article 501 requirements for use in Class 1, Groups A, B, C, & D,

Division 2 & Article 505 – Class I, Zone 2, A Ex nA IIC T4 hazardous location areas.

Warning:

DO NOT TAKE COVER OFF OR DISASSEMBLE MONITOR MOTORS. If cover

is/has been removed, the warranty is void and the service life of the motor is
significantly reduced.

Advertising