Installation guide & pressing instructions, Minimum spacing – Elkhart Products Corporation (EPC) APOLLOXPRESS User Manual

Page 3

Advertising
background image

For additional inf

orma

tion, submittal sheets and manuals

, visit w

ww

.apollo

valv

es

.com

APOLLO VALVES Customer Service (704) 841-6000

62

www.apollovalves.com

InSTALLATIOn GUIDE & PRESSInG InSTRUCTIOnS

MInIMUM SPACInG

Between APOLLOXPRESS® Joints

To prevent distortion of the pipe, fittings require a minimum distance
between fittings (refer to chart below). Failure to provide this distance
may result in an improper seal.

fitting Size Minimum Spacing
1/2”

0”

¾”

0”

1”

0”

1 ¼”

1/2”

1 1/2”

5⁄8”

fitting Size Minimum Spacing
2”

¾”

2 1/2”

5⁄8”

3”

5⁄8”

4”

5⁄8”

Between an APOLLOXPRSS® Joint and Existing Solder Joint

The minimum distance when making an APOLLOXPRESS® joint near
a solder joint is in the table below. No residual solder, flux, or debris
should be on the tubing.

Tube Dia. Minimum Distance
1/2”

¼”

¾”

¼”

1”

7⁄16”

1 ¼”

7⁄16”

1 1/2”

5⁄8”

Tube Dia. Minimum Distance
2”

¾”

2 1/2”

¼”

3”

¼”

4”

¼”

Between an APOLLXPRESS® Joint and Existing Brazed Joint

The minimum distance when making an APOLLOXRESS® joint near a
brazed joint is 2 pipe diameters of the tube being pressed.

Tube Dia. Minimum Distance
1/2”

1”

¾”

1 1/2”

1”

2”

1 ¼”

2 1/2”

1 1/2”

3”

Tube Dia. Minimum Distance
2”

4”

2 1/2”

5”

3”

6”

4”

8”

When Soldering near an APOLLOXPRESS® Joint

Minimum distance is found in the table below. The installer shall take
proper precautions to protect and keep cool the APOLLOXPRESS® joint
using one of the following methods.
• Wrap joint in a cold wet rag.
• Use a spray type spot freezing product. The product should NOT
come into contact with the joint.
• Prefabricate the solder connection, waiting for it to cool and then
make the press connection.

Tube Dia. Minimum Distance
1/2”

1 1/2”

¾”

2 ¼”

1”

3”

1 ¼”

3 ¾”

1 1/2”

4 1/2”

Tube Dia. Minimum Distance
2”

6”

2 1/2”

7 1/2”

3”

9”

4”

12”

When Brazing near an APOLLOXPRESS® Joint

Stay at least 12 inches away from the pressed connection. The
installer shall take proper precautions to protect and keep cool the
APOLLOXPRESS® joint using one of the following methods.
• Wrap joint in a cold wet rag.
• Use a spray type spot freezing product. The product should NOT
come into contact with the joint.
• Prefabricate the brazed connection, waiting for it to cool and then
make the press connection.

Advertising