ERICO CADDY ROD LOCK Bottom-Mount Duct Bracket User Manual

Caddy® rod lock bottom-mount duct bracket

Advertising
background image

2-1/2 [64mm]

Slot Width

3/4" [19mm]

Typical

Duct Width

+1-1/2" [38mm]

Bottom of duct

Push bracket on

to threaded rods

Duct Height

Duct Width

"L" DIMENSION

Maximum Open Position

Rotate lock nut counter clockwise

until reaches stopping position

Step 2:

Lift duct into place.

Step 1:

Install six (6) self-

drilling screws

(included) at

marked location

on bracket.

Rectangular Duct Application

*Note: (4) screws are required for non-duct application.

**CRLD37BEG (3/8") and CRLDM10BEG (M10) were verified by the

SMACNA Testing and Research Institute to be acceptable alternatives

to the duct hanger systems described in the ANSI

®

/SMACNA HVAC

Duct Construction Standards (HVAC-DCS) 3rd edition, Chapter 5,

Tables 5-1 and 5-1M

Step 0:

***P/2 = (Duct Height) + (Duct Width)

Max. Half of

Duct

Perimeter***

3/8", M8, M10 Threaded Rod Sizes**

"L" Dimension

P/2 = 30"

L = 10ft [3m] L = 8ft [2.4m]

L = 5ft [1.5m]

P/2 = 72"

P/2 = 96"

P/2 = 120"

--

P/2 = 168"

--

--

P/2 = 192"

--

--

Part Number

Article

Number

Rod Size

Load Rating for

general applications*

(3.0 safety factor)

CRLD37BEG

N/A

3/8"

600 lbs [2,650 N]

CRLDM8BEG

390015

M8

600 lbs [2,650 N]

CRLDM10BEG

390016

M10

600 lbs [2,650 N]

TECHNICAL SUPPORT:

www.erico.com

CFS473_F

INSTRUCTION SHEET

1 OF 2

© 2013, 2014 ERICO International Corporation.

CADDY® ROD LOCK

Bottom-Mount Duct Bracket

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.

5.

All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any

6.

other purpose.

NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for:

a. Conformance to all governing codes.

b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified

engineer.

c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
ANSI is a registered trademark of American National Standards Institute

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

Advertising