grounding system

refer to Detail "A"

Suggested three radial grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench

approximately 0.8m deep. The conductor is laid in the trench and is connected to ground rods. The

conductor in each trench is encased in GEM material. Ground rods must extend 3m below ground

level.

4.6m FRP Support Mast

(ERICO Part # FRP4.6MBLACK)

Guy Kit

(ERICO Part # GUYKIT7M/GRIP)

Do not over-tension guy wires

(Slightly sagging)

Inline Coupling

(ERICO Part # I/LCOUPL)

ERICO DYNASPHERE

(ERICO Part # D/SMKIV-SS)

Guy Ring

(ERICO Part # GUYRING)
ERICORE Downconductor

with factory-fitted

upper termination

4.6m FRP Mast Base

(ERICO Part # MBFRP4.6M)

ERICORE Downconductor

ERICORE Downconductor

Saddle

(ERICO Part # CONSAD/E2)

Saddle Mounting Screws

(ERICO Part # CONSADFX)

Typical MBFRP4.6M Base Plate

4 HOLES, Ø12.5mm

175mm

225mm

®

Typical Upper Termination

Not to Scale

Lightning Event Counter

(ERICO Part # LECIV)
ERICORE Downconductor
ERICO CADWELD

Connection or

mechanical connection
Ground Inspection Well

Crow's Foot

(ERICO Part # GF302)

2/0 Conductor

(3 x 20 FT [6.1M] length)

Enclosed in GEM material

Minimum 5/8" x 8' [16mm x 2.4M] long

ground rod in four locations

Lightning Event Counter

Refer to installation manual

for alternate locations

(ERICO Part # LECIV)

Preferred Angle

45 -60

Top View

TECHNICAL SUPPORT

www.erico.com

IP79155_A

1 OF 1

INSTRUCTION SHEET

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

ERICO DYNASPHERE MKIV

Installation Instructions for 4.6m FRP Guyed Mast

© 2014

ERICO International Corporation.

Advertising
Table of contents