ERICO ER Series 5m Stainless Steel Cantilevered Mast User Manual

Detail "a

Advertising
background image

3.3FT [1M]

Mast Detail

2 Holes, 0.43 [10.9mm]

1.57 [39.9mm]

3.54 [89.9mm]

4.72 [119.9mm]

Not to Scale

Typical ALOF1GS Wall Bracket Base

2

-

Note: This is one of several alternative installation methods.

Refer to ERICO installation handbook for more details.

Typical LPC126R Cable Strap

(ERICO Part # A930W004) Drive-in Type Anchor

(ERICO Part # LPC126R) Copper Cable

(ERICO Part # LPC805) Copper Strap

Not to Scale

Mast Adapter

(ERICO Part # INTCPTSIIER2)

Stainless Steel Mast

(ERICO Part # ER22000SS)

Bonding Clamp

(ERICO Part # LPC570)

Stainless Steel Cable Tie

(ERICO Part # CABTIESS)

Three every 3.3FT [1M]

Mast Support Bracket

(ERICO Part # ALOF1GS)

For complete

grounding system

refer to Detail "A"

Two downconductors

are required

Lightning Event Counter

Refer to installation manual

for alternate locations

(ERICO Part # LECIV)

SI INTERCEPTOR

(ERICO Part # SI25i, SI40i or SI60i)

Suggested triangular grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench

20FT [6.1M] in length and approximately 2.5FT [0.8 M] deep. 20FT [6.1M] of 2/0 conductor is laid in

the trench and is connected to the ground rod using "GY" CADWELD connection. The conductor in

each trench is encased in ERICO GEM material. Ground rods must extend 10FT [3M] below ground

level.

®

2/0 Conductor

(3 x 20FT [6.1M] length)

Enclosed in

ERICO GEM material

Bond to the existing

building ground system

Detail "A"

Lightning Event Counter

(ERICO Part # LECIV)

ERICO CADWELD "GR" Connection

or mechanical connection

(ERICO Part # LPC790)

Downconductor

(ERICO Part # LPC126R)

Ground Inspection Well

Minimum 5/8" X 8' [16mm X 2.4M] long

ground rod in three locations

LPC570 Bronze Pipe Bonding Clamp

Installing contractor to field

adjust and insure a secure bond

on highest ER series mast

LPC126R Copper Cable

®

Not to Scale

1

-

End View

®

®

-

2

1

-

3

-

-

2

1

-

3

-

Stainless Steel Mast

(ERICO Part # ER33000SS)

ER33000SS

ER22000SS

INTCPTSIIER2

3

-

3.3FT [1M]

TECHNICAL SUPPORT

www.erico.com

IP79108_B

1 OF 1

INSTRUCTION SHEET

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

ERICO INTERCEPTOR SI25i, SI40i or SI60i

Installation Instructions for 5m Stainless Steel Cantilevered Mast - ER Series

Terminal Elevation: 4m Above Structure

© 2006, 2014

ERICO International Corporation.

3.3FT [1M]

Advertising
Table of contents