ERICO ER Series 7m Stainless Steel Guyed Mast User Manual

Detail "a, Detail "b

Advertising
background image

®

Detail "A"

Preferred Angle

45° - 60°

Guy Kits

(ERICO Part # GUYKIT7M/GRIP)

(ERICO Part # GUYKIT4M/GRIP)

Do not over-tension guy wires

(Slightly sagging)

Stainless Steel Mast

(ERICO Part # ER11000SS)

Bonding Clamp

(ERICO Part # LPC570)

Mast Adapter

(ERICO Part # INTCPTSIIER2)

Stainless Steel Mast Base

(ERICO Part # ER3BASESS)

Refer to Detail "B"

SI INTERCEPTOR

(ERICO Part # SI25i, SI40i or SI60i

ER33000SS

ER3BASESS

Detail "B"

4 HOLES, Ø1/2 [12.5mm]

9 [229mm]

7 [178mm]

INTCPTSIIER1

1

-

®

-

2

Not to Scale

(ERICO Part # LPC805) Copper Strap

(ERICO Part # LPC126R) Copper Cable

(ERICO Part # A930W004) Drive-in Type Anchor

Typical LPC126R Cable Strap

Ground Inspection Well

Downconductor

(ERICO Part # LPC126R)

Lightning Event Counter

(ERICO Part # LECIV)

Bond to the existing

building ground system

ERICO CADWELD "GR" Connection

or mechanical connection

(ERICO Part # LPC790)

®

®

2/0 Conductor

(3 x 20FT [6.1M] length)

Enclosed in

ERICO GEM material

Minimum 5/8" X 8' [16mm X 2.4M] long

ground rod in three locations

Lightning Event Counter

Refer to installation manual

for alternate locations

(ERICO Part # LECIV)

Two downconductors

are required

Not to Scale

LPC126R Copper Cable

LPC570 Bronze Pipe Bonding Clamp

Installing contractor to field

adjust and insure a secure bond

on highest ER series mast

Suggested triangular grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench

20FT [6.1M] in length and approximately 2.5FT [0.8M] deep. 20FT [6.1M] of 2/0 conductor is laid in the

trench and is connected to the ground rod using "GY" CADWELD connection. The conductor in

each trench is encased in ERICO GEM material. Ground rods must extend 10FT [3M] below ground

level.
Note: This is one of several alternative installation methods.

Refer to ERICO installation handbook for more details.

Mast Detail

For complete

grounding system

refer to Detail "A"

Stainless Steel Mast

(ERICO Part # ER23000SS)

ER11000SS

2

-

1

-

Stainless Steel Mast

(ERICO Part # ER33000SS)

Stainless Steel

Cable Tie

(ERICO Part # CABTIESS)

Three every 3.3FT [1M]

ER23000SS

TECHNICAL SUPPORT

www.erico.com

IP79121_B

1 OF 1

INSTRUCTION SHEET

CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.

WARNING:

ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at

1.

www.erico.com and from your ERICO customer service representative.

ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.

2.

All instructions must be completely followed to ensure proper and safe installation and performance.

3.

Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property

4.

damage, serious bodily injury and death.

SAFETY INSTRUCTIONS:

All governing codes and regulations and those required by the job site must be observed.

Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.

ERICO INTERCEPTOR SI25i, SI40i or SI60i

Installation Instructions for 7m Stainless Steel Guyed Mast - ER Series

© 2006, 2014

ERICO International Corporation.

Advertising
Table of contents