ETC Unison Fluorescent Option Kit User Manual

E t c, Unison, Fluorescent option kit installation

Advertising
background image

E T C

®

S e t u p G u i d e

Unison

®

Fluorescent Option Kit Installation

Unison Fluorescent Option Kit Setup Guide

Page 1 of 2

Electronic Theatre Controls, Inc.

Corporate Headquarters

3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA

Tel +608 831 4116

Fax +608 836 1736

London, UK

Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK

Tel +44 (0)20 8896 1000

Fax +44 (0)20 8896 2000

Rome, IT

Via Pieve Torina, 48, 00156 Rome, Italy

Tel +39 (06) 32 111 683

Fax +44 (0) 20 8752 8486

Holzkirchen, DE

Ohmstrasse 3, 83607 Holzkirchen, Germany

Tel +49 (80 24) 47 00-0

Fax +49 (80 24) 47 00-3 00

Hong Kong

Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong

Tel +852 2799 1220

Fax +852 2799 9325

Service: (Americas)

[email protected]

(UK)

[email protected]

(DE)

[email protected]

(Asia)

[email protected]

Web:

www.etcconnect.com

Copyright © 2012 ETC. All Rights Reserved.

Product information and specifications subject to change.

7183M2220

Rev C

Released 2012-02



ETC intends this document to be provided in its entirety.

.

It is best to install rack options after conduit rough-in and the line, load and control terminations

are complete to reduce the likelihood of damage to the option board.

Fluorescent Option Kit

Install the Fluorescent Option Kit

The fluorescent option (DRd-FLO) kit provides 24 outputs for control of 4-wire (0-10 Vdc)

fluorescent ballasts. Each channel output is linked one - to - one with a rack circuit for power

control. The FLO board is comprised of 24 individual 0 - 10 Vdc connections, each rated to

control a maximum of 400mA per channel (typically 50 or more ballasts).

Each output connection is clearly labeled on the removable screw terminal bus connectors. The

removable connectors accept 12 - 24 AWG (4 - .25mm

2

) Class 1 wire.

Step 1:

Align the FLO option board to the mounting studs in the bottom of the DRd rack.

• Notice the mounting holes on the FLO option board. One is a slotted keyhole,

another is an open ended slot and the remaining two on the other end of the

board are standard mounting holes used to secure the board in place.

Step 2:

Set the rear stud through the slotted keyhole and align the open ended slot with the

back right side mounting stud.

Step 3:

Gently slide the FLO board toward the right I/O board aligning the five prong

connector to the receptacle on the right I/O board.

Step 4:

Secure the remaining two mounting holes to the pems with the screws provided.

N o t e :

A single Unison DRd rack supports the use of either the DALI option kit or the FLO

option kit, but not both in the same rack.

Step 2:

Step 3:

Step 4: