E T C I n s t a l l a t i o n G u i d e

Unison Paradigm

®

Light Sensor

Unison Paradigm Light Sensor Installation Guide

Page 1 of 8

Electronic Theatre Controls, Inc.

Corporate Headquarters

3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA

Tel +608 831 4116

Fax +608 836 1736

London, UK

Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK

Tel +44 (0)20 8896 1000

Fax +44 (0)20 8896 2000

Rome, IT

Via Pieve Torina, 48, 00156 Rome, Italy

Tel +39 (06) 32 111 683

Fax +44 (0)20 8752 8486

Holzkirchen, DE

Ohmstrasse 3, 83607 Holzkirchen, Germany

Tel +49 (80 24) 47 00-0

Fax +49 (80 24) 47 00-3 00

Hong Kong

Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong

Tel +852 2799 1220

Service: (Americas)

[email protected]

(UK)

[email protected]

(DE)

[email protected]

(Asia)

[email protected]

Web:

www.etcconnect.com

Copyright © 2012 ETC. All Rights Reserved.  Product information and specifications subject to change.

7184M2170  Rev A  Released 2012-12  ETC intends this document to be provided in its entirety.

Overview

The Unison Paradigm

®

Light Sensor provides light level measurement to the

connected Paradigm control system. The control system receives the measurements
to maintain a programmed lighting output in both dimmed and switched lighting
systems.

The Paradigm Light Sensors are available in three models:

P-LS - Light Sensor with Controller

P-LSC - Light Sensor Controller Only

P-LSH - Light Sensor Only

Each controller supports an individual pair of Light Sensors and is available in neutral
white or black finish.

A light sensor may be installed within the controller or installed remotely, using up to
1,000 feet (304m) of 16 AWG wire per controller. When using a pair of light sensors,
both sensors transmit their light readings to a single controller which provides an
averaged reading to the connected Paradigm control system.

Wire Specification

Controller

The Paradigm Light Sensor utilizes LinkConnect to power the sensor and to provide
data to and from the connected Paradigm control system.

LinkConnect is topology-free and polarity independent. You can install your data runs
in any desired combination of bus, star, loop, and home-run. ETC recommends using
Belden 8471 (or equivalent) wire. The total combined length of a LinkConnect wire
run may not exceed 1,640 feet (500m), with a maximum distance of 1,312 feet (400m)
between any two devices.