Ces-az-ubs-01b with standard read head – EUCHNER CES-AZ-UBS-01B (Multicode) User Manual

Page 13

Advertising
background image

Operating Instructions Safety System CES-AZ-UBS-01B

13

CES-AZ-UBS-01B with standard read head

Important!

To achieve category 3 according to EN ISO 13849-1, it is necessary to monitor
the downstream contactors (here contacts of -K3 and -K4 in the feedback loop).
This example shows only an excerpt that is relevant for connection of the CES
system. The example illustrated here does not show complete system planning.
The user is responsible for safe integration in the overall system.

If only one enable path is to be used for control (e. g. of downstream contactors),
failures involving a short circuit between the contacts on the enable path and, for
example, the power supply must be excluded.

With reference to EN ISO 13849-2 Table D.5, this exclusion can be provided if

Ì

the cables are inside an electrical installation space and

Ì

the enclosure meets the related requirements (see EN 60204-1 or IEC 60204-1).

This example shows only an excerpt that is relevant for connection of the CES
system. The example illustrated here does not show complete system planning.
The user is responsible for safe integration in the overall system.

24VDC

GND

-A1

24VDC

-F1

24V

0V

CES-AZ-UBS-01B

100412

TST

EUCHNER

OUT ERR GND

SH1

K1

+

Read-

head

H11

Trans-

ponder

K2

+

H12

13

14

-V1

24V

-F2

23

24

-K3

-V2

-K4

L1

M

3

~

-M1

L2

L3

11

12

21

22

feedback loop

PLC