System manual safety system ces-a-c5, System status table – EUCHNER CES-A-C5H-01 (Unicode) User Manual

Page 19

Advertising
background image

System Manual Safety System CES-A-C5...

19

System Status Table

Operating mode

Actuator/ Guar

d position

Safety outputs LA and LB

PLC

LED display

Output

State

Output

OUT (status signal)

ST

ATE (gr

een)

OUT/ERROR (yellow)

OUT/ERROR (r

ed)

Normal operation

closed

on

1

Normal operation, door closed

open

off

0

Normal operation, door open

Setup

open

off

0

4 Hz

Initial setup after delivery, ready for first teach-in operation

closed

off

0

1 Hz

(60 s)

Teach-in operation

closed

off

0

Positive acknowledgement of completion of teach-in operation

To activate the actuator code from the teach-in operation in the evalu-

ation unit, the operating voltage must then be switched off at the

evaluation unit for min. 3 seconds.

State indication

X

off

0

3 x +

Indication after 1st to 5th teach-in operation

X

off

0

 x +

Indication of the remaining teach-in operations after the 6th teach-in

operation

X

off

0

1 x +

Indication of the remaining teach-in operations after the 7th teach-in

operation

X

off

0

Device cannot perform any further teach-in operation

Fault display

X

off

0

Device-internal component failure or

excessively high interference (EMC) or short circuit/external power at

the LA/LB safety output

Operating fault

closed

off

0

1 x

Incorrect 9th teach-in operation

closed

off

0

 x

Incorrect teach-in operation for an old actuator

closed

off

0

3 x

Negative acknowledgement for teach-in operation. Actuator was held

in front of the read head for less than 60 s

Key to symbols

N

0 Volt or not connected

1

4 Volt

0

0 Volt

LED is not lit

LED is lit

15 Hz (8 s)

LED flashes for 8 seconds with 15 Hz

3 x +

LED flashes three times and then lights up continuously

3 x

LED flashes three times, and this is then repeated

X

Any state