Operating Instructions Safety Switch CES-I-AP-U-C04

20

Typical system times

Ready delay: After switching on, the unit carries out a self-test for 0.5 s. The

system is ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time from the moment

when the actuator is at the operating distance (safety door closed) to the moment

when the safety outputs switch on T

on

is 300 ms.

Risk time according to EN 60947-5-3: If an actuator moves outside the

operating distance, the safety outputs FO1A and FO1B are deactivated after a

maximum of 260 ms.
Difference time: The safety outputs FO1A and FO1B switch with a slight delay
in relation to each other. They have the same signal state at the latest after a dif-
ference time of 10 ms.
Test pulses at the safety outputs: The device generates its own clock signal on
the output lines FO1A/FO1B. A downstream control system must tolerate these

test pulses, which may last up to 0.3 ms (applies for a load with C < 30 nF and

R < 20 kΩ).
This can usually be set up in the control systems by parameter assignment. If

parameter assignment is not possible for your control system or if shorter test

pulses are required, please contact our support organization.

Dimension drawings

10,6

M12x1

42

4,

1

29

,2

25

8

32

10,6

4,

1

12

,9

ca. 100/220

15,5

14,5

4,

8

18

Active face

LEDs

Active

face

LEDs

With M8 plug connector

Connection cable

with flying lead

Connection cable with M12 plug connector

Rubber support

(included)

With rubber support