Operating Instructions Safety Switches CES-AR-C.2-AH

15

Connection of a single CES-AR-C

If a single CES-AR-C is used, connect the switch as shown in Figure 3. The OUT 

output can also be connected here to a control system as a monitoring output.
The switch can be reset via the RST input. To do this, a voltage of 24 V is applied 

to the RST input for at least 3 seconds. The RST input must be connected to 0 V 

if it is not used.

Important!

The subsystem CES-AR complies with PL e in accordance with EN 13849-1. To 
integrate the subsystem in a category 3 or 4 structure, it is necessary to monitor 
the downstream load (the feedback loop must be monitored).
These examples show only an excerpt that is relevant for connection of the CES 
system. The example illustrated here does not show complete system planning. 
The user is responsible for safe integration in the overall system.

GND

DC 24 V

CES-AR-C #1

IB

1

UB
2

OA
3

OB
4

Plug connector (8-pin)

OUT
5

IA

6

0V

7

RST
8

WH

BN

GN

YE

GY

PK

BU

RD

-K1

-K2

-M1

M

A1

A2

A1

A2

13

14
13

14

Fig. 3: Connection example for a single CES-AR-C