Operating Instructions Safety Switch CES-I-AR-M-C04

6

Function

The device complies with the following safety requirements:

Ì

Safety category 4, PLe according to EN ISO 13849-1

Ì

Redundant design of the circuit in the unit with self-monitoring

Ì

This means that the safety system still functions even if an internal component

fails

Ì

The switch state of the semiconductor outputs is continuously monitored inter-

nally

Ì

Short circuit detection at the safety outputs by pulsed signals

The following switch-on condition applies for the safety outputs FO1A and FO1B

(see also System status table and section Typical system times):

Ì

Safety guard closed

Ì

Both safety inputs FI1A and FI1B must be switched on.

The CES system consists of the following components: coded actuator (transpon-

der) and switch.
Every EUCHNER actuator supplied has an electronic coding (unique coding) that is

read by the read head. Only if a correct coding is detected does the system accept

the actuator. The code in an actuator cannot be reprogrammed.
Unlike systems with unique code detection, on the CES-I-AP-M-C04 a specific code

is not polled but instead it is only checked whether the actuator is of a type that can

be detected by the system (multicode detection). There is no exact comparison of

the actuator code with the code defined in the safety switch (unique code detection).
The safety switch is fastened to the fixed part of the safety guard.
The actuator attached to the movable part of the safety guard is moved towards

the read head fitted in the safety switch by closing the door. When the switch-on

distance is reached, power is supplied to the actuator by the read head by induc-

tion and data can be transferred.
If a permissible code is detected, the safety outputs are released. Independent of

the safety outputs, monitoring output OD switches on as soon as the actuator is

in the operating distance.
Due to the combination of dynamic polling of the actuator and the redundant,

diverse design of the safety electronics with the two feedback safety outputs, the

safety switch will enter the safe state with every detectable fault.
When the safety guard is opened, the safety outputs switch off the safety circuit

and the monitoring output OD is switched off. The state of the safety outputs is

monitored internally by two microprocessors.
If faults are detected, the safety circuit is switched off and the DIA LED illuminates.

In case of devices with a monitoring output OI, the output is switched on.
The safety switch has a redundant circuit design with self-monitoring. This means

that the safety system is still effective even if a component fails.