Operating Instructions ESL

15

Connection of several ESL devices in an AR switch

chain

Important!

Ì

A switch chain may contain a maximum of 20 safety switches.

Ì

In the estimation of the PL for the overall system, a maximum value of
100 years can be assumed for the MTTF

d

according to the limit value in

EN ISO 13849-1:2008, section 4.5.2. This corresponds to a minimum value
for the PFH

d

of 2.47x10

-8

/h.

The devices are connected in series using plug connectors and Y-distributors. If

a safety door is opened or if a fault occurs on one of the switches, the system

shuts down the machine. A higher level control system can, however, not detect

which safety door is open or on which switch a fault has occurred.
The switches can be reset via the RST input. To do this, a voltage of 24 V is applied

to the RST input for at least 3 seconds. The supply voltage to the switches is inter-

rupted during this time. The RST input must be connected to 0 V if it is not used.

Figure 5: Connection example for series connection of several ESL-AR devices

GND

DC 24 V

Stift/
connector
(male)

1
2
3
4
5

1

ESL-AR #n

1

2

2

3

3

4

4

Y-Verteiler/Y-distributor

M12 plug-connector

(8-pin)

5

5

6

6

7

Buchse/
connector
(female)

7

8

8

1
2
3
4
5

Stift/
connector
(male)

1
2
3
4
5

1

ESL-AR #n-1

1

2

2

3

3

4

4

Y-Verteiler/Y-distributor

M12 plug-connector

(8-pin)

5

5

6

6

7

Buchse/
connector
(female)

7

8

8

1
2
3
4
5

Stift/
connector
(male)

1
2
3
4
5

1

ESL-AR #1

1

2

2

3

3

4

4

Y-Verteiler/Y-distributor

M12 plug-connector

(8-pin)

5

5

6

6

7

Buchse/
connector
(female)

7

8

8

1
2
3
4
5

1
2
3
4
5

Stift/
connector
(male)

Kurzschlussstecker/

Short-circuit plug

FI1B

UB

FO1A

FO1B

OD

FI1A

0V

RST

FI1B

UB

FO1A

FO1B

OD

FI1A

0V

RST

Connected

load

FI1B

UB

FO1A

FO1B

OD

FI1A

0V

RST