EUCHNER ESM-BA2xx User Manual

Emergency stop safety relay esm-ba2, User information

Advertising
background image

1

User Information

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

Emergency Stop Safety Relay ESM-BA2..

Cyclical monitoring of the output contacts

Indication of the switching state via LED

2 start behaviors possible:

- Monitored manual start

- Automatic start

Up to PL e, SILCL 3, category 4

It is not allowed to open the device, tamper with the devi-
ce or bypass the safety devices.

All relevant safety regulations and standards are to be
observed.

The overall concept of the control system in which the
device is incorporated must be validated by the user.

Failure to observe the safety regulations can result in
death, serious injury and serious damage.

Correct Use

The ESM-BA2.. is a universal emergency stop safety switching
device with two safe relay outputs that can quickly and safely
stop the moving parts of a machine or system in case of danger.

Applications for the ESM-BA2.. include single or dual-channel
emergency stop circuits and guard monitoring on machines and
systems.

Features

2 safe, redundant relay outputs

Connection of:

- Emergency stop buttons
- Safety switches
- Non-contact safety switches

- OSSD-Outputs

Single and dual-channel operation possible

Feedback loop for monitoring downstream contactors or
expansion modules

Function

The emergency stop safety switching device ESM-BA2.. is
designed for safe isolation of safety circuits according to
DIN EN 60204-1 and can be used up to safety category 4,
PL e according to DIN EN ISO 13849-1.

The internal logical system closes the safety contacts when
the start button is pressed.

When the emergency stop circuit is opened, the positively
driven safety contacts are opened and safely switch the
machine off. It is ensured that a single fault does not lead
to a loss of the safety function and that every fault is detec-
ted by cyclical self-monitoring no later than when the sys-
tem is switched off and switched on again.

Electrical
Connection

When the 24 V version is used, a safety transformer
according to EN 61558-2-6 or a power supply unit with
electrical isolation from the mains must be connected.

External fusing of the safety contacts (4A slow-blow or
6A quick-action or 10A gG) must be provided.

A maximum length of the control lines of 1000 meters
with a line cross section of 0.75 mm

2

must not be excee-

ded.

The line cross section must not exceed 2.5 mm

2

.

If the device does not function after commissioning, it
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty.

Installation

As per DIN EN 60204-1, the device is intended for installa-
tion in control cabinets with a minimum degree of protection
of IP54. It is mounted on a 35-mm DIN rail according to
DIN EN 60715 TH35.

Safety Precautions

Installation and commissioning of the device must be
performed only by authorized personnel.

Observe the country-specific regulations when installing
the device.

The electrical connection of the device is only allowed to
be made with the device isolated.

The wiring of the device must comply with the instructi-
ons in this user information, otherwise there is a risk that
the safety function will be lost.

Fig. 1 Block diagram ESM-BA2..

Fig. 2 Installation / removal

Fig. 3 Connections

A1:

Power supply

A2.

Power supply

S11:

DC 24 V control voltage

S10:

Control line

S21:

Start control line

S13:

Control line

S14:

Control line

S12:

Control line

13-14:

Safety contact 1

23-24:

Safety contact 2

(not for the plug-in terminals)