EUCHNER ESM-2H2 Series User Manual

Hand safety relay, series esm-2h2, User information

Advertising
background image

User Information

1

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

2-Hand Safety Relay, Series ESM-2H2..

Up to PL e, SILCL 3, category 4

Correct Use

The ESM-2H2.. 2-hand safety relay is an extremely
compact, universal safety two-hand control unit. It
complies with EN574, Typ III C, and is intended for use
in safety circuits that are designed in accordance with
EN 60204-1, e.g. on presses, punches and bending
tools. Due to the internal error monitoring, the 2-hand
safety relay can be used, despite very compact dimen-
sions, for all applications up to the highest safety cate-
gory 4 and PL e according to EN ISO 13849-1, SILCL 3
according to EN 62061 or Typ III C according to EN 574.

Features

2 safe, redundant relay outputs

Cyclical monitoring of the output contacts

Feedback loop for monitoring downstream contactors or
expansion modules

Short circuit and earth fault monitoring

Extrem compact housing

Function

The EUCHNER 2-hand safety relay ESM-2H2.. is suitable
for setting up and monitoring two-hand circuits and is used
to protect the operators. Dangerous work steps can only be
triggered when both two-hand buttons connected are ope-
rated simultaneously, i.e. within 0.5s.

It is to be ensured a single fault or a malfunction does not
result in the loss of the safety function and every fault is
detected by the cyclic self-monitoring at the latest prior to
the next actuation.

When the operating voltage is applied to A1-A2 and the
feedback loop X1-X2 is closed, the ESM-2H2.. is ready for
use. To be able to initiate a switching operation, the output
relays must be de-energized. The output relays only switch
to the energized position when the two-hand buttons T1
and T2 are operated simultaneously, i.e. within 0.5s.

Fig. 1 Block diagram ESM-2H2..

It is not allowed to open the device, tamper with the devi-
ce or bypass the safety devices.

All relevant sefety regulations and standards are to be
observed.

The overall concept for the control system in which the
device is integrated is to be validated.

Failure to observe the safety regulations can result in
death, serious injury and serious damage.

Installation

As per DIN EN 60204-1, the device is intended for installa-
tion in control cabinets with a minimum degree of protection
of IP54. It is mounted on a 35-mm DIN rail according to
DIN EN 60715 TH35.

Safety Precauti-
ons

Installation an setup are only allowed to be undertaken
by trained personell.

The electrical connection is only allowed to be made with
the device and wiring isolated.

The wiring must comply with the instructions in this user
information, otherwise there is a risk that the safety
function will be lost.

As per EN 60204-1 the device is intended for installation
in control cabinets with a minimum degree of protection
of IP54.

Fig. 2 Installation/removal

Electrical Connec-
tion

When the 24V version is used, a safety transformer
according to EN 61558-2-6 or a power supply unit with
electrical isolation from the mains must be connected.

External fusing of the safety contacts (4A slow-blow or
6A quick-action or 10A gG) must be provided.

A maximum length of the control lines of 1000 meters
with a line cross section of 0.75 mm

2

must not be excee-

ded.

The line cross section must not exceed 2.5 mm

2

.

If the device does not function after commissioning, it
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty.

Fig. 3 Connections

A1:

Power supply

A2.

Power supply

S11:

Control line T1

S12:

Control line T1

S13:

Control line T1

S21:

Control line T2

S22:

Control line T2

S23:

Control line T2

X1; X2:

Feedback loop

13-14:

Safety contact 1

23-24:

Safety contact 2

(not dor plug-in terminals)

The output relays are not switched if:

only one two-hand button is actuated or the time between the actuation of the 2 two-hand buttons is greater than 0.5s,

the feedback loop is open (fault in the external contactor),

another error (short circuit, cable break, error in the switching device) has occurred.

When T1 and/or T2 are/is released, the output relays opens immediately. In order to trigger a new operation, both two-hand

buttons must first be released and the feedback loop must be closed.