3 troubleshooting, Led state flashes twice (separate operation), Troubleshooting – EUCHNER CET User Manual

Page 5: Cet help for setup and service, 1 led state flashes twice (separate operation)

Advertising
background image

CET Help for Setup and Service

Page 5 of 10

Subject to technical modifications

01/2013

3 Troubleshooting

3.1

LED STATE flashes twice (separate operation)

Fault symptom:

The CET-AR displays the fault state “input error (e.g. missing test pulses)”.
Possible fault causes:

24 V DC missing at inputs I

A

and/or I

B

A safety evaluation unit or a safe control system with pulsing outputs is connected the inputs I

A

and/or I

B

.

Remedy:
1. Check the wiring and correct it if necessary or switch the clock pulses off
2. Switch the voltage off

or
Press the reset button (if present) that controls the integrated reset input

3. Switch the voltage on again

or
Release the reset button

4. Wait until LED STATE flashes three times or stops flashing entirely (after approx. 8 s)
5. Close the safety door

The CET-AR is now operational again, the LED STATE stops flashing