Wind

Velocity

Building

Height

Roof Deck

Field

Membrane

Fastener

Density

≤ 100 mph

≤ 40’

Steel, Lightweight Concrete, Structural
Concrete, Wood Plank

12’ wide

12” o.c.

≤ 75’

Steel, Lightweight Concrete, Structural
Concrete, Wood

10’ wide

12” o.c.

≤ 75’

Cementitious Wood Fiber , Gypsum

8’ wide

12” o.c.

100 to 119

mph

≤ 40’

Steel, Lightweight Concrete, Structural
Concrete, Wood Plank

12’ wide

6” o.c. or 12”

o.c.

≤ 50’

Steel, Lightweight Concrete, Structural
Concrete, Wood

10’ wide

12” o.c.

≤ 40’

Structural Concrete

12’ wide

12” o.c.

≤ 75’

Structural Concrete

10’ wide

12” o.c.

≤ 50’

Cementitious Wood Fiber , Gypsum

8’ wide

12” o.c.

120 to 129

mph

≤ 75’

Steel, Lightweight Concrete

8’ wide

12” o.c.

≤ 50’

Structural Concrete

10’ wide

12” o.c.

≥ 130 mph

≤ 75’

Steel, Lightweight Concrete

10’ wide

6” o.c.

≤ 50’

Structural Concrete

8’ wide

12” o.c.

Notes:

1. Lightweight Insulating Concrete Decks must be installed over a steel deck.. The fasteners
must penetrate through the steel deck.
2. Cementitious Wood Fiber, Gypsum and Wood Decks are not acceptable for a mechanically
attached roof system installation in the ≥ 130 mph wind zone.

Fastener Pullout Requirements:

It is recommended that withdrawal resistance tests be performed when considering specifying a
mechanically attached roof system. If the installation is to be a retrofit or recover project the existing
roofing material must be removed to the deck and the pullout test performed to the uncovered deck. The
test is to be performed by a qualified and experienced individual certified by the fastener manufacturer.
Fastener installations must be tested in various locations of the roof including corner and perimeter areas.
A roof plan should be included with the submittal documenting the location of each pullout test and the
associated values. The following values are the minimum withdrawal resistance required for the roof
system installation.

Deck Type

Min. Pullout Value

System


Steel 22 gauge or heavier

500 lbs.

Mechanically Fastened

360 lbs.

Adhered


Steel lighter than 22 gauge

300 lbs.

Adhered only


Lightweight Concrete on Steel

360 lbs.

Mechanically Fastened

Adhered


Structural Concrete

800 lbs.

Mechanically Fastened

Wood

360 lbs.

Mechanically Fastened

250 lbs.

Adhered

Cementitious
Wood Fiber or Gypsum

300 lbs.

Mechanically Fastened