The cable shield must not be used as the signal ground.

It is tempting to try and reduce the cost of 5-wire cabling by using a 4-wire cable

with the shield used as the signal ground. DON’T DO IT. The initial cost savings

are always exceeded by the maintenance costs once the system is operating under

field conditions. It is often necessary to completely replace the network com-link

with the proper cable (5-wire plus shield) to eliminate noise problems in the system.
The signal ground must not be connected to the chassis or earth ground.

The chassis or earth ground is intended as a safety ground for power supplies, EMI

filters, voltage spike protection circuits, 120 VAC neutral returns, and all manner of

AC and DC driven devices. As a result, the chassis or earth ground can carry large

voltage potentials and currents. Connecting the signal ground to chassis or earth

ground can damage the devices connected to the com-link.

2.4. Set Jumper for 3-Wire RS-422/485

This step is required only if the OIT will be communicating with the host controller

using RS-485 half-duplex 3-wire communication.

STEPS

1. Remove the protective cover from the rear of the unit.
CAUTION: When the rear cover is removed, the circuitry inside is exposed to

possible damage by electrostatic discharge. Refer to Static Awareness on page 4.
2. Locate jumper “JP4” using Figure 7 as a guide. The jumper is installed on

the upper two pins of a 3-pin header. This is called Position “A”.

3. Move the jumper to the lower two pins of the 3-pin header (Position “B”).

Ensure that the jumper is pressed fully into place.

4. Replace the rear cover and the four retaining screws.

INSTALLATION MANUAL

13

1010-0046A, REV 00

JP4

B

A

Normal

A

Position "A",

Half-Duplex 3-Wire

Position "B",

JP4

RS485

B

(Display)

(CPU Board)

B

JP4

A

Figure 7 MAP450D Jumper Installation