10. Error messages

If an error is detected, then a corresponding error message appears which

must be acknowledged by pressing any key. Possible error messages are

as follows:

ER.01 The switching points and hystereses/switch-back points are not within

the permissible setting range.

Example:

A switching point is set to 180 bar, the hysteresis to 200 bar.

The setting is not correct since the resulting switch-back point is

smaller than the switching point: the error message is displayed.

Action: Correct the settings.

ER.10 A data error has been detected in the saved settings. Possible causes

are strong electromagnetic interference or a component fault.

Action: Check all the settings (programming enable, switching points, switch-

back points and basic settings) and correct these if necessary. If the

error occurs frequently, please contact Hydac Service.

ER.12 An error has been detected in the stored calibration data.

Possible causes are strong electromagnetic interference or a

component fault.

Action: After acknowledging the error, the unit will continue to operate, with

reduced accuracy, until it is switched off. However, check all important

settings (switching points, switch-back points and basic settings) and

correct these if necessary. The unit must in any case be returned to

the manufacturer for re-calibration or repair.