Hydrolevel 170 Series User Manual

Page 2

Advertising
background image

A1

Connect the hot lead of the input volt-

age (24 VAC, 60 HZ) to terminal 1. Connect the
neutral lead to terminal 2. 24 VAC, 60 HZ must
be supplied to terminals 1 and 2 for internal
operation of the control.

Connect terminal 2 to burner

A2

circuit neutral. Connect terminal P2 to burner
circuit in series with other limit controls.
Consult boiler manufacturer instructions for
proper terminal connections. Control should be
wired in series with and before other circuits.

P1

P2

A

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

NEUTRAL

HOT

2

1

ALARM

P1

P2

A

HOT

BURNER
CIRCUIT

NEUTRAL

2

1

BURNER

POWER

SOURCE

(24 or

120VAC)

P1

P2

A

NEUTRAL

HOT

BURNER

+

0

LIMIT

CONTROLS

2

1

2

P1

P2

A

BURNER

POWER

SOURCE

24 VAC

1

NEUTRAL

HOT

FACTORY

INSTALLED

JUMPER

1

P1

P2

A

ALARM

2

P2

A

24VAC

1

NEUTRAL

HOT

P1

P1

P2

A

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

HOT

NEUTRAL

2

1

WIRING METHOD A: SAME POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

B1

WARNING! Remove the jumper

between 1 and P1. Connect the hot lead of the
input voltage (24 VAC, 60 HZ) to terminal 1.
Connect the neutral lead to terminal 2. 24 VAC,
60 HZ must be supplied to terminals 1 and 2 for
internal operation of the control.

Connect hot lead from the 24 VAC

B2

or 120 VAC burner power source to terminal P1.
This terminal supplies power to terminal P2 in
normal operating conditions when water is at
the probe. Connect neutral to burner circuit.
Note: consult boiler manufacturer instructions
for proper terminal connections.

A3

Optional alarm connection. Connect

alarm common to terminal 2. Connect alarm hot
to terminal A.

Upon completion of wiring, replace control
box cover.

B3

Connect terminal P2 to burner

circuit in series with and before other limit con-
trols.

Optional alarm connection. Connect

B4

alarm hot to terminal A. Connect alarm common
to neutral of the burner power source.

Upon completion of wiring, replace control
box cover.

A1

A2

A3

B1

B3

B2

B4

WIRING METHOD B: SEPARATE POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

WARNING: Be sure to
remove the jumper
between 1 and P1.