WIRING TO 24 VAC TRANSFORMER

For boilers using a standard 24 VAC transformer

BOILER SPECIFIC MODELS AND WIRE HARNESSES

Connect RED wire to

hot side of 24 Volt boiler trans-

former (R). Connect WHITE wire to common side of

24 Volt boiler transformer (C). Connect the GREEN

wire to any suitable, unpainted ground screw.

Note: for operation of the control, the green wire

must be connected to a ground source electrically

common with boiler ground.

Cut-off the connectors and strip the ends of the two

yellow wires of the Model 1100 harness. Break into

the burner circuit between the

hot side of the trans-

former (R) and other limit controls. Connect either

YELLOW wire to the

hot side. Connect the other

YELLOW wire in series with other limit controls.

Important: The switch contacts of the low water cut-

off (yellow wires) must be wired in series with all

other limit and operating controls (as shown above).

Step

Step

1100H2

Including 45-348 Harness

Part No. Model

Description

45-1100 1100

1100 with standard wire harness (cable 45-531-54)

45-1102 1100H2 1100 with wire harness for UTC intergrated control module

(cable 45-348)

45-1103 1100H3 1100 without wire harness

45-1104 1100H4 1100 with wire harness for Burnham Alpine, SCG/PVG

(cable 45-350)

45-1105 1100H5 1100 with wire harness for Weil McLain Ultra, Lochinvar

Knight & Solution (cable 45-349)

45-1106 1100H6 1100 with wire harness for Burnham Series 2, PVGA, PVCGA,

New Yorker CG-D and PVCGA (cable 45-347)

Note: Wire Harnesses are also sold separately (use cable part numbers above)