INFICON I/O1000 I/O module User Manual
Page 12
12
Description
6 - FUSE and DIP switch S1, S2
Fuses for digital outputs and DIP switches (under the cover)
Fuses for digital outputs 1 ... 4 and 5 ... 8:
2 x 0.75 A (Schurter: 7010.9800.xx)
1 = ON, 0 = OFF, – = not used
1 = ON, + = switching OFF -> ON in operation, – = not used, x = no meaning
7 - LD
Connection for the data cable to the mass spectrometer module
8 - ANALOG IN
Analog input (input voltage range 0 V to 10.8 V)
Connection plug arrangement
DIP switch S1
4321
Factory setting
(default value of the interface protocol by MS module/control unit)
-000
ASCII protocol
-010
LD protocol
-011
Binary protocol
-101
LDS1000 protocol
-110
DIP switch S2
4321
Activate boot mode for software update
x+––
Disable bus terminator 120 Ω for RS-485
1x––
1
24V supply (output)
2
GND to 24V supply
3
Analog input (0 V to 10.8 V)
4
GND to analog input